52
Coding in the delivered condition
Possible change
Min. pump speed
E7:30
Minimum speed of the
variable speed heating
circuit pump: 30 % of the
maximum speed (only for
weather-compensated
control units)
E7:0
to
E7:100
Minimum speed adjustable
from 0 to 100 % of the max-
imum speed
Screed function
F1:0
Screed drying function
disabled (only for
weather-compensated
control units)
F1:1
to
F1:6
Screed drying function
adjustable in accordance
with 6 optional tempera-
ture/time profiles (see
page 127)
F1:15
Constant flow temperature
20 °C
Party mode time limit
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h (only for weather-
compensated control
units)
*1
F2:0
No time limit for party
mode
*1
F2:1
to
F2:12
Time limit adjustable from 1
to 12h
*1
Pump control in "Only DHW"
F6:25
In the "DHW only" oper-
ating mode, the circula-
tion pump in the heating
circuit connection set is
permanently ON (only for
constant temperature
control units)
F6:0
In the "DHW only" operat-
ing mode, the circulation
pump in the heating circuit
connection set is perma-
nently OFF
F6:1
to
F6:24
In the "DHW only" operat-
ing mode, the circulation
pump in the heating circuit
connection set will be star-
ted 1 to 24 times per day for
10 min respectively
*1
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5692 843 GB