130
Raising the reduced room temperature
During operation with reduced room
temperature, the reduced set room tem-
perature can be automatically raised
subject to the outside temperature. The
temperature is raised in accordance with
the selected heating curve, but no higher
than the set standard room tempera-
ture.
The outside temperature limits for the
start and end of the temperature raising
can be adjusted via coding addresses
"F8" and "F9".
Example using the settings in the delivered condition
A
B
-20
Outside temperature in °C
Boiler water or Flow temperature in °C
80
70
60
50
40
30
0
-5 -10 -15
5
10
Set room temperature in °C
35
30
25
20
15
10
5
0
90
A
Heating curve for operation with
standard room temperature
B
Heating curve for operation with
reduced room temperature
Function description
Control functions
(cont.)
5692 843 GB