29
B
C
A
Fig. 18
1.
Check the joints between flue gas collector
A
and
boiler back panel for tightness.
Note
Check the gaskets at full load operation, for exam-
ple using an inspection mirror, gas sensor or ther-
mal image camera. If required, remove the thermal
insulation components. Traces of condensate on
the outside of flue gas collector
A
also indicate a
leak.
2.
Check the flue gas temperature sensor and plug-in
connection
B
for correct seating.
3.
Check gasket
C
with the boiler flue connection for
tightness. If necessary, replace the gasket.
Performing final checks
Enter the actual values into the report.
Checking the safety valve function
Checking the mixer for ease of operation and leaks
1.
Remove the motorised lever from the mixer han-
dle.
2.
Check the mixer for ease of operation.
3.
Check the mixer for tightness. Replace the O-ring
seals if the mixer leaks.
4.
Click the motorised lever into place.
Commissioning, inspection, maintenance
Checking the gaskets on the flue gas side
(cont.)
5833296