64
Boiler
Vitocrossal, type
CRU 800
CRU 1000
Rated heating output range
P
n
: T
F
/T
R
80/60 °C
kW
125 to 750
156 to 938
P
cond
: T
F
/T
R
50/30 °C
kW
137 to 800
171 to 1000
Rated heating input range Qn
(Sized for up to mean
sea level (MSL) 1500 m)
kW
127 to 762
159 to 952
Boiler product ID
CE-0085CS0411
Permiss. operating temperature
°C
95
95
Permiss. flow temperature
(safety temperature)
°C
110
110
Heating surface
m
2
24.2
31.5
Max. permiss. operating pressure
bar
6
6
MPa
0.6
0.6
Min. permiss. operating pressure
bar
0.5
0.5
MPa
0.05
0.05
Test pressure
bar
7.8
7.8
MPa
0.78
0.78
Boiler body dimensions
Total length
mm
2241
2441
Length of the combustion chamber module
mm
1019
1219
Length of the heat exchanger module
mm
1272
1272
Width
mm
960
960
Height
mm
1676
1676
Total dimensions
incl. casing
Length
mm
3187
3389
Width
mm
1060
1060
Height
mm
1676
1676
Foundation dimensions
Length
mm
2500
2700
Height
mm
1200
1200
Weight
Combustion chamber module
kg
535
585
Heat exchanger module
kg
615
615
Burner
kg
120
120
Total weight, dry
kg
1435
1492
Water capacity
l
1150
1180
Connections
Boiler flow
PN 6 DN
100
100
Boiler return 1
*1
PN 6 DN
100
100
Boiler return 2
*1
PN 6 DN
100
100
Safety connection (male thread)
R
2
2
Drain (male thread)
R
1
¼
1
¼
Condensate drain (male thread)
R
½
½
Gas flow rate, natural gas E (G20)
at 15 °C, 1.013 bar
■
At rated heating output
m
3
/h
80.6
100.8
■
At partial load
m
3
/h
13.4
16.8
*1
When connecting 2 heating circuits, connect the heating circuit with the higher temperature level to boiler return 2.