66
MatriX-Disk burner
Vitocrossal, type
CRU 800
CRU 1000
Rated heating output range
P
n
: T
F
/T
R
80/60 °C
kW
125 to 750
156 to 938
P
cond
: T
F
/T
R
50/30 °C
kW
137 to 800
171 to 1000
Rated heating input range Qn
(Sized for up to mean
sea level (MSL) 1500 m)
kW
127 to 762
159 to 952
Burner type
MDI
Burner product ID
CE-0085CS0412
Voltage
, 3/N/PE
V
400
400
Frequency
Hz
50
50
Current
, max
A
16
16
Power consumption
■
At rated heating output
W
1500
2000
■
At partial load
W
100
100
Gas supply pressure
■
Natural gas E and natural gas LL
mbar
kPa
18 to 25
1.8 to 2.5
Sound power level
to EN 15036
dB(A)
83
85