Vitocrossal 300 CU3A 26 to 199 Service
Coding 2
DHW
(continued)
Coding in the factory setting
Possible change
65:0
DO NOT ADJUST
65:0
to
65:3
--
67:40
For solar DHW heating:
Set DHW temperature
104°F (40°C). Reheating is
suppressed above the selected
set temperature.
67:0
to
67:95
Set DHW temperature
adjustable from 32°F to 203°F
(0°C to 95°C) (limited by boiler-
specific parameters)
6F:100
Maximum output for DHW
heating in %, specified by
the boiler coding card
6F:0
to
6F:100
Maximum output for DHW heating
adjustable from minimum output
to 100%.
71:0
DHW recirculation pump: “ON”
in accordance with the time
program
71:1
“OFF” during DHW heating
to first set value.
71:2
“ON” during DHW heating
to first set value.
72:0
DHW recirculation pump: “ON”
in accordance with the time
program
72:1
“OFF” during DHW heating
to second set value.
72:2
“ON” during DHW heating
to second set value.
73:0
DHW recirculation pump: “ON”
in accordance with the time
program
73:1
to
73:6
“ON” from once per hour for 5
minutes up to 6 times per hour
for 5 minutes during the time
program.
73:7
Constantly “ON”.