Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
70
Coding 2
DHW
Coding in the factory setting
Possible change
56:0
Set DHW temperature
adjustable from 50 to 140°F
(10 to 60°C)
56:1
Set DHW temperature adjustable
from 50°F to over 140°F (10°C
to over 60°C).
Note:
Maximum value subject to
boiler coding card. Observe
the maximum permissible
DHW temperature [max.
154°F (68°C)].
57:0
DO NOT ADJUST
--
--
58:0
Without auxiliary function for
DHW heating
58:10
to
58:60
Input of a second set DHW
temperature, adjustable from
50°F to 140°F (10°C to 60°C)
(observe coding addresses “56”
and “63”).
59:0
DHW tank heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable from 1
to 10 K below the set value.
5B:0
DHW tank directly connected
to the boiler
5b:1
DHW tank connected downstream
of the low loss header.
5E:0
Circulation pump for DHW tank
heating stays in control mode
at signal
“External blocking”
5E:1
Circulation pump for DHW tank
heating stops at signal “External
blocking”.
5E:2
Circulation pump for DHW tank
heating starts at signal “External
blocking”.
5F:0
Circulation pump for DHW tank
heating stays in control mode
at signal
“External demand”
5F:1
Circulation pump for DHW tank
heating stops at signal “External
demand”.
5F:2
Circulation pump for DHW tank
heating starts at signal “External
demand”.
60:20
During DHW heating, the boiler
water temperature is maximum
20 K higher than the set DHW
temperature
60:5
to
60:25
The differential between the boiler
water temperature and the set
DHW temperature is adjustable
from 5 to 25 K.
62:2
Circulation pump with 2 minutes
run-on time after DHW tank
heating
62:0
Circulation pump without run-on.
62:1
to
62:15
Run-on time adjustable from 1 to
15 minutes.