Vitocrossal 300 CU3A 26 to 199 Service
5673 649 - 18
30
Check Gas Pipes and Fittings for Leaks
1. Remove the motorized lever from the mixing valve
handle.
2. Check the mixing valve for ease of operation.
3. Check the mixing valve for leaks. Replace the O-rings
if the mixing valve leaks.
4. Snap the motorized lever into place.
Service
Checking the Mixing Valve for Obstructions and Leaks
CAUTION
Ensure all joints of gas line are pressure tight and that
gas valves do not leak when under normal operating
pressure (use approved leak detection liquid).
WARNING
The gas supply piping must be leak tested before placing
the boiler in operation.
WARNING
Escaping gas leads to a risk of explosion.
Check gas equipment for tightness.
Note:
For the tightness test, use only suitable and
approved leak detecting agents and devices.
Leak detecting agents with unsuitable contents
(e.g. nitrites, sulphides) can lead to material
damage. Remove residues of the leak detecting
agent after testing.
Check Electrical Connections
Ensure all plug-in connectors and strain reliefs make
positive contact and are seated properly.
Refer to the Installation Instructions