111
5673 649 - 18
Vitocrossal 300 CU3A 26 to 199 Service
Additional Information
Technical Data
Boiler Model No. CU3A
26, 94
35, 125
45, 160
57, 199
Natural Gas / Liquid Propane Gas
CSA input
CSA output / DOE heating capacity*
1
MBH
(kW)
MBH
(kW)
19-94
(5.6-27.5)
17.7-87
(5.2-25.5)
25-125
(7.3-36.6)
23.3-116
(6.8-34)
43-160
(12.6-47)
40-149
(11.7-43.7)
43-199
(12.6-58)
40-185
(11.7-54.2)
Net AHRI Rating
MBH
(kW)
76
(22)
101
(30)
129
(38)
161
(47)
Heat exchanger surface area
ft.
2
(m
2
)
16.7
(1.5)
20.7
(1.9)
34.1
(3.2)
34.1
(3.2)
Min. gas supply pressure
Natural gas
Liquid propane gas
“w.c.
“w.c.
4
10
4
10
4
10
4
10
Max. gas supply pressure
*3
Natural gas
Liquid propane gas
“w.c.
“w.c.
14
14
14
14
14
14
14
14
A.F.U.E.
%
95
95
95
95
Weight
lbs
(kg)
269
(122)
275
(125)
352
(160)
352
(160)
Boiler water content
USG
(L)
13.5
(51)
13.0
(49)
18.8
(71)
18.8
(71)
Max. operating pressure
at 210ºF (99ºC)
psig
(bar)
30
(2)
30
(2)
30
(2)
30
(2)
Boiler water temperature
- Adjustable high limit (AHL) range
space heating (steady state)
DHW production
- Fixed high limit (FHL)
ºF
(ºC)
ºF
(ºC)
ºF
(ºC)
68-194
(20-90)
194
(90)
210
(99)
68-194
(20-90)
194
(90)
210
(99)
68-194
(20-90)
194
(90)
210
(99)
68-194
(20-90)
194
(90)
210
(99)
Boiler connections
Boiler heating supply and return
Pressure relief valve
Boiler drain
Gas valve connection
NPTM
NPTF
NPTM
NPTF
1
a
in.
¾
in.
1
in.
¾
in.
1
a
in.
¾
in.
1
in.
¾
in.
1
a
in.
¾
in.
1
in.
¾
in.
1
a
in.
¾
in.
1
in.
¾
in.
*1
Output based on 140ºF (60ºC), 120ºF (49ºC) system supply/return temperature.
*2
Net AHRI rating based on piping and pick-up allowance of 1.15.
*3
If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator
must be installed upstream of the heating system.
Note:
For high altitude installation at 10,000 ft. the input for model Vitocrossal 300 CU3A will have an altitude
de-ration of 18%.