194
If, on site, only
one
pump and
one
three-
way diverter valve are used to switch
between DHW heating and central heat-
ing mode, parameter "
Heat/DHW
diverter v
" must be changed to "
Yes
".
"Yes"
Three-way diverter valve is
installed; secondary pump
also runs for DHW heating.
"No"
Three-way valve is not instal-
led; DHW is heated via a sep-
arate output; secondary
pump does not run; circula-
tion pump for cylinder heating
(heating water side) is star-
ted.
Menu
■
"Device settings"
■
"Programming"
■
"Internal hydraulics"
■
"Heat/DHW diverter valve"
Delivered condition
No
Setting
Yes/No
Control settings, hydraulics
Operation with three-way diverter valve
5414 828 GB
Содержание VITOCAL 350-A
Страница 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Страница 57: ...57 3x 8 9 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB Installation ...
Страница 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Страница 60: ...60 4 mm 4x 4x 4x 3 2 1 2 2 Installation sequence Fitting the silencer hoods only type AWH O 5414 828 GB ...
Страница 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Страница 63: ...63 Type AWH O 2 3 4 5 4x 1 Installation sequence Installing the heat pump cont 5414 828 GB Installation ...
Страница 115: ...115 Fitting the front panel 1 2 Installation sequence Closing the heat pump cont 5414 828 GB Installation ...
Страница 227: ...227 053 032 039 034 038 033 034 039 040 027 Parts lists Parts list type AWH I cont 5414 828 GB Service ...
Страница 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Страница 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Страница 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...