9
5608 012 v1.1
Vitocrossal 200 CM2 Technical Data
Cylinder Burner
Specifications
Boiler Model CM2
186
246
311
Product ID
see boiler
Voltage
V
120
120
120
Frequency
Hz
60
60
60
Power consumption
at max. input
W
225
278
368
at min. input
W
51
52
67
Version
modulating
Dimensions
Length
in. (mm)
30.3 (770)
30.3 (770)
30.3 (770)
Width
in. (mm)
21.5 (546)
21.5 (546)
21.5 (546)
Height
in. (mm)
18.9 (482)
18.9 (482)
18.9 (482)
Weight
Burner only
Burner package (with kits, flanges and
mounting hardware)
lb. (kg)
lb. (kg)
61.0 (27.6)
93 (42.2)
64.5 (29.3)
100.5 (45.5)
64.5 (29.3)
100.5 (45.5)
Min. gas supply pressure
Natural gas
“w.c.
4
4
4
Liquid propane gas
“w.c.
10
10
10
Max. gas supply pressure
Natural gas
“w.c.
14
14
14
Liquid propane gas
“w.c.
14
14
14
Gas connection
NPT
1
1
a
1
a
Specifications