Vitocrossal 200 CM2 Technical Data
Specifications
Technical Data
(continued)
Boiler Model
CM2
186
246
311
Boiler Water Content
USG
81
77
74
(L)
(306)
(292)
(279)
Heat exchanger surface
ft.
2
73.2
90.4
114.1
water cooled
(m
2)
(6.8)
(8.4)
(10.6)
Maximum Operating Temperature
°F
190
190
190
(°C)
(88)
(88)
(88)
Maximum Operating Pressure
psig
75
75
75
(kpa)
(517)
(517)
(517)
Boiler Connections
Boiler supply and return (BS), (BR)
in.
2
b
2
b
2
b
(ANSI flanges)
(mm)
(65)
(65)
(65)
Safety Supply
in.
1
a
1
a
1
a
(mm)
(32)
(32)
(32)
Boiler Drain
in.
1
1
1
Condensate Drain
in.
c
c
c
Vent pipe
Internal Diameter
in.
8
8
8
(mm)
(201)
(201)
(201)
Flue Gas Values
temperature (at a return
temperature of 86° F (30° C)
at rated input
°F
136
132
130
(°C)
(58)
(55)
(54)
at partial load
°F
95
95
95
(°C)
(35)
(35)
(35)
Temperature (at a return
temperature of 140° F (60° C)
at rated input
°F
167
167
167
(°C)
(75)
(75)
(75)
Mass flow rate (of flue gas)
at rated input
lbs/h
593
785
994
(kg/h)
(269)
(356)
(451)
at partial load
lbs/h
198
262
331
(kg/h)
(90)
(119)
(150)
Pressure
at boiler flue outlet
pa
70
70
70
at rated input
“w.c.
0.28
0.28
0.28