Vitocrossal 200 CM2 Technical Data
Specifications
Recommended Minimum Service Clearances
Mechanical room
Avoid air contamination by halogenated hydrocarbons
(e.g. as in sprays, paints, solvents and cleaning agents)
Avoid very dusty conditions
Avoid high levels of humidity
Protect against frost and ensure good ventilation,
otherwise the system may suffer faults and damage.
In rooms where air contamination from halogenated
hydrocarbons is to be expected, operate the boiler
only in balanced flue mode.
Minimum clearances to combustibles
Boiler model CM2
186
246
311
Top
0
Sides
0
Flue
As per vent manufacturer’s specifications
Front
0
Floor
combustible
Legend
A
Boiler
B
Burner
*1
Can be zero clearance, if serviceability and burner
swing position is not required.
*2
Clearance for vent pipe installation.
To enable convenient installation and maintenance,
observe the stated clearance dimensions. Maintain the
minimum clearances where space is tight.
In the delivered condition, the boiler door hinge bracket
is factory installed on the left side of the door. If required,
the boiler door hinge bracket can be reinstalled on the
right side of the door.
CM2
186
246
311
a
*1
in. (mm)
20 (500)
20 (500)
20 (500)
b
*2
in. (mm)
30 (760)
30 (760)
30 (760)
c in. (mm)
20 (500)
20 (500)
20 (500)
d in. (mm)
20 (500)
20 (500)
20 (500)
e in. (mm)
24 (600)
24 (600)
24 (600)
f in. (mm)
11 (280)
11 (280)
11 (280)
g in. (mm)
15
b
(395)
15
b
(395)
15
b
(395)