4
5608 012 v1.1
Vitocrossal 200 CM2 Technical Data
Technical Data
Specifications
Boiler Model
CM2
186
246
311
Input
MBH
663
878
1112
(kW)
(194)
(257)
(326)
Minimum Input
MBH
133
175
222
(kW)
(39)
(51)
(65)
Output
*
1
MBH
(kW)
643
(188)
851
(249)
1078
(316)
Net AHRI rating
MBH
(kW)
559
(164)
740
(217)
937
(275)
Combustion efficiency
*
1
%
95
95
95
Thermal efficiency
*
1
%
97
97
97
Overall length(e)
in.
73
73
73
(mm)
(1852)
(1852)
(1852)
Overall width (c)
in.
36
b
36
b
36
b
(including insulation)
(mm)
(930)
(930)
(930)
Overall height (a)
in.
66
66
66
(including control unit)
(mm)
(1676)
(1676)
(1676)
Concrete boiler base
Length
in.
40
40
40
(mm)
(1005)
(1005)
(1005)
Width
in.
31
31
31
(mm)
(800)
(800)
(800)
Thickness
in.
4
4
4
(mm)
(100)
(100)
(100)
Weight
Boiler body
lb
503
536
564
(Kg)
(228)
(243)
(256)
Complete with the burner, control
lb
726
759
792
and thermal insulation
(Kg)
(329)
(344)
(359)
Note:
For high altitude installations (5,000 to 10,000 ft.), the input will have an altitude de-ration of 15% for 5,000 ft.
and 18% for 10,000 ft.
*
1