60
Parameter
Setting
Further enabling for Vitovent 300-F, if applicable:
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"1"
"Enable reheater bank hydraulic 7D02"
"1"
"Enable humidity sensor 7D05"
"1"
"Enable CO2 sensor 7D06"
"1"
Further enabling for Vitovent 200-C, if applicable:
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"1"
Frost protection with preheating
coil, defrosting via bypass
"2"
Frost protection with preheating
coil, comfort function
"Strategy passive frost protection 7D2C"
"0"
Fans OFF
"1"
Defrosting via bypass
"2"
Supply air fan OFF
"Mounting position 7D2F"
"0"
Ceiling mounting
"1"
Wall mounting
If necessary, set values:
"Ventilation"
Ó
"Set extract air temperature 7D08"
(only in conjunction with
Vitovent 300-F)
"100"
to
"300"
(
≙
10 to 30 °C)
"Flow rate reduced ventilation 7D0A"
Subject to sizing
Ventilation unit service instruc-
tions
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Heat pump cascade
Parameters for heat pump cascade
Setting
Lead heat pump
Lag heat pump
"System scheme 7000"
"0"
to
"10"
"11"
"Cascade control 700A"
"2"
"0"
"Number of lag heat pumps 7029"
"1"
to
"4"
—
"Number of heat pump in cascade 7707"
—
"1"
to
"4"
LON communication module installed
"Enable LON communication module 7710"
"1"
"1"
"LON system number 7798"
"1"
to
"5"
"1"
to
"5"
"LON subscriber number 7777"
Each number can only be allocated once.
"1"
to
"99"
"1"
to
"99"
"LON fault manager 7779"
Only one control unit
per system may be configured as the
fault manager.
"0"
or
"1"
"0"
or
"1"
"Source time 77FE"
"0"
"1"
"Send time 77FF"
"1"
"0"
"Source outside temperature 77FC"
"0"
"1"
"Send outside temperature 77FD"
"1"
"0"
"Interval for data transfer via LON 779C"
"20"
"20"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5787 232 GB