59
Parameters for ice store system
Parameter
Setting
"System definition"
Ó
"Select primary source 7030"
"1"
"External extension 7010"
"2"
"Solar"
Ó
"Type solar control unit 7A00"
"2"
Possibly set additional parameters.
"System definition"
Ó
"Start hysteresis solar air absorber 7031"
"0"
to
"500"
(
≙
0 to 50 K)
"Min. runtime to suppress summer mode 7035"
"0"
to
"1440"
min
"Last calendar week for summer mode 7036"
Calendar week
"1"
to
"53"
Parameters for utilisation of power generated on site
Parameters
Setting
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"1"
"Threshold for electrical power 7E04"
"0"
to
"300"
(
≙
0 to 30 kW)
Enable functions for utilisation of power generated on site.
"Photovoltaics"
Ó
"Enable own energy consumptn for set DHW temperature 2
7E10"
"1"
"Enable own energy consumption for DHW heating 7E11"
"1"
"Enable own energy consumptn for heating water buffer cyl.
7E12"
"1"
"Enable own energy consumption for heating 7E13"
"1"
"Enable own energy consumption for cooling 7E15"
"1"
Specify the temperature differential to the selected set value for the chosen function.
"Photovoltaics"
Ó
"Raise set DHW cylinder temperature PV 7E21"
"0"
to
"500"
(
≙
0 to 50 K)
"Raise set heating water buffer cylinder temp PV 7E22"
"0"
to
"400"
(
≙
0 to 40 K)
"Raise set room temperature PV 7E23"
"0"
to
"100"
(
≙
0 to 10 K)
"Reduce set room temperature PV 7E25"
"0"
to
"100"
(
≙
0 to 10 K)
Parameters for ventilation
Parameter
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Vitovent 300-F
"2"
Vitovent 200-C
"Heat exchanger type 7D2E"
"0"
Countercurrent heat exchanger
"1"
Enthalpy heat exchanger
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5787 232 GB