86
Commissioning without the commissioning wizard
Activating the service menu
The service menu can be activated from
any other menu.
Hold down
OK
+
å
simultaneously for
approx. 4 s.
Disabling the service menu
The service menu remains active until it
is disabled with
"Terminate service?"
,
or if it is not used for 30 minutes.
Setting parameters using the "Sys-
tem scheme" example
To set a parameter, first select the
parameter group and then the parame-
ters.
All parameters are displayed as plain
text. A parameter code is also assigned
to each parameter.
Service menu:
1. Hold down
OK
+
å
simultaneously
for approx. 4 s.
2. Select
"Coding level 1"
.
3. Select parameter group:
"System
definition"
4. Select parameter:
"System scheme
7000"
5. Set system scheme:
"6"
Alternatively, if the service menu was
already active:
Extended menu
1.
å
2.
"Service"
3. Select
"Coding level 1"
.
4. Select parameter group:
"System
definition"
5. Select parameter:
"System scheme"
6. Confirm parameter code:
"7000"
7. Set system scheme:
"6"
Required parameters for components connected on site
Detailed explanations on
parameters
Vitotronic 200 heat pump control
unit service instructions
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5848 164 GB
Содержание BW 301.A090
Страница 44: ...44 A Frame screw Installation sequence Siting the heat pump cont 5848 164 GB...
Страница 157: ...157 5848 164 GB...
Страница 158: ...158 5848 164 GB...
Страница 159: ...159 5848 164 GB...