88
Coding in the delivered condition
Possible change
Lock out controls
8F:0
Operation enabled in
standard menu and ex-
tended menu.
Note
The respective code is
only activated when you
exit the service menu.
8F:1
Operation blocked in
standard menu
and
exten-
ded menu.
Emissions test mode can
be enabled.
8F:2
Operation enabled in
standard menu and
blocked in extended
menu.
Emissions test mode can
be enabled.
Set flow temperature for external demand
9b:70
Set flow temperature for
external demand 70 °C
9b:0
to
9b:127
Set value adjustable from 0
to 127 °C (limited by boiler-
specific parameters)
"Boiler"
Select group
"Boiler"
(see page 85).
Coding
Coding in the delivered condition
Possible change
Burner service in 100 hours
21:0
No service interval (hours
run) selected
21:1
to
21:100
The number of hours run
before the burner should
be serviced is adjustable
from 100 to 10 000 h.
One adjusting step
≙
100 h
Service interval in months
23:0
No interval for burner
service
23:1
to
23:24
Interval adjustable from 1
to 24 months
Code 1
"General"
(cont.)
5773 238 GB
Содержание B2UA
Страница 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Страница 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Страница 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Страница 13: ...13 24 22 23 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Страница 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Страница 15: ...15 28 2x 2x 29 30 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Страница 21: ...21 Removing the front panels 2 4 2x 1 3 5 Installation sequence Installing the boiler 5773 238 GB Installation ...
Страница 22: ...22 Siting and levelling the boiler 1 2 SW17 Installation sequence Installing the boiler cont 5773 238 GB ...
Страница 29: ...29 2x 4x 4 3 5 2 1 Installation sequence Opening the control unit casing 5773 238 GB Installation ...
Страница 39: ...39 5 4 2 6 2x 3 1 Installation sequence Closing the control unit casing 5773 238 GB Installation ...
Страница 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Страница 185: ...185 0010 0004 0001 0003 0004 0005 0009 0006 0007 0008 0007 0002 Parts lists Cylinder module cont 5773 238 GB Service ...
Страница 199: ...199 5773 238 GB ...