Viessmann AirflowPLUS AH2A Installation, Operating and Service
5680 011 -10
34
Setting Fan Speed
(continued)
Installation
Note:
Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings.
The above values are approximations only, actual results may vary.
Note:
Factory switch set positions are shown in bold.
AH2A-385 Viessmann AirflowPLUS Air Handler
3/4 hp ECM - Air Flow Selectable Options
Set at dip switch S2.
Heat Fan Speed Switches 1 & 2
OFF
OFF
1650
ON
OFF
1590
OFF
ON
1470
ON
ON
1320
Adjust Fan Speed Switches 3 & 4
OFF/OFF
ON/OFF
OFF/ON
OFF/OFF
ON/OFF
OFF/ON
Heating CFM
1650
1800
1480
1590
1750
1430
Cooling CFM
1875
2060
1680
1730
1900
1560
Heating CFM
1470
1620
1320
1320
1450
1180
Cooling CFM
1620
1780
1450
1500
1650
1350
Cool Fan Speed Switches 5 & 6
OFF
OFF
1875
ON
OFF
1730
OFF
ON
1620
ON
ON
1500
Cool Fan Speed Profiles Switches 7 & 8
Pre-Run
Time Min.
Motor %
Short Run
Time Min.
Motor %
Motor OFF
Time Min.
Motor %
OFF
OFF
5
82
2
88
2
75
ON
OFF
3
82
2
88
2
75
OFF
ON
2
82
-
-
4
75
ON
ON
-
-
-
-
4
75