Viessmann AirflowPLUS AH2A Installation, Operating and Service
5680 011 -10
46
Power is on at the air handler.
The air handler internal water
coil freeze sensor is activated by
three extreme low temperature
cycles. Alarm buzzer sounds
continuously.
The red light is illuminated
on the housing.
Sensor T3 flash code indicates
7 green then 7 green.
Buzzer is also ON.
The alarm buzzer can be silenced
by cycling the power to the
air handler OFF then ON.
Cooling lockout active, cooling
can only be reactivated by cycling
the power OFF and then ON.
Inadequate air flow, plugged filter,
extreme ESP, low refrigerant.
Outdoor ambient or
thermostat set too low.
Yes
Yes
Yes
Yes
Yes
Continue
Continue
No
Observe each sensor code and
record related flash codes as
shown on the housing mounted
LED. Refer to page 42.
Cooling lockout
This feature is initiated if three freeze protect cycles occur
within a single cooling cycle or, if three freeze cycles
occur when a cooling cycle is not in progress.
A freeze protect cycle is when the air handler integral
A/C coil freeze sensor is triggered by unacceptably low
discharge air temperatures.
Troubleshooting
(continued)