Domestic hot water
Parameters

Code

Delivered condition Commission-

ing

Maintenance/
service

"Set DHW temperature"

6000

500 (

 50 °C)

 

 

"Min. DHW temperature"

6005

100 (

 10 °C)

 

 

"Max. DHW temperature"

6006

600 (

 60 °C)

 

 

"Hysteresis DHW temperature heat
pump"

6007

50 (

 5 K)

 

 

"Hysteresis DHW temperature booster
heater"

6008

100 (

 10 K)

 

 

"Start optimisation for DHW heating"

6009

0

 

 

"Stop optimisation for DHW heating"

600A

0

 

 

"Set DHW temperature 2"

600C

600 (

 60 °C)

 

 

"Temperature sensor at bottom of DHW
cylinder"

600E

0

 

 

"Enable booster heaters for DHW heat-
ing"

6014

0

 

 

"Enable electric heaters for DHW heat-
ing"

6015

1

 

 

"Priority DHW heating with combi cylin-
der"

6016

0

 

 

"Start attempts for DHW after high pres-
sure shutdown"

6017

1

 

 

Electric booster heater
Parameters

Code

Delivered condition Commission-

ing

Maintenance/
service

"Enable instantaneous heating water
heater"

7900

1

 

 

"Enable electric heaters for DHW heat-
ing"

7901

0

 

 

"Enable instant. heating water heater for
central heating"

7902

1

 

 

"Max. output instantaneous heating wa-
ter heater"

7907

3

 

 

"Output for instant. heating water heater
at power-OFF"

790A

0

 

 

"Dual mode temp. instant. heating water
heater"

790B

500 (

 50 °C)

 

 

Internal hydraulics
Parameter

Code

Delivered condition Commission-

ing

Maintenance/
Service

"Heat pump for drying a building"

7300

0

 

 

"Time program for screed drying"

7303

0

 

 

"Flow temperature for external demand"

730C

500 (

 50 °C)

 

 

"Starting time high efficiency circulation
pump"

7365

Do not adjust

Commissioning/service reports

Control parameters report

 (cont.)

5700 542 GB

Appendix

Содержание 7513685

Страница 1: ...201 B04 to B13 201 C10 to C16 Air source heat pump split version for heating operation Type AWB AC 201 B04 to B13 201 C10 to C16 Air source heat pump split version for heating and cooling operation F...

Страница 2: ...olate the system from the power supply e g by removing the separate fuse or by means of a mains isolator and check that it is no longer live Note In addition to the control circuit there may be severa...

Страница 3: ...unit Overview of connections 24 Internal unit Main PCB function components 230 V 25 Internal unit Expansion PCB on main PCB function components 230 V 27 Internal unit Luster terminals signal and safe...

Страница 4: ...B04 82 8 Parts list for external unit 230 V type AWB AWB AC 201 B05 B07 Ordering parts 85 Parts external unit 230 V type AWB AWB AC 201 B05 B07 86 9 Parts lists for external unit 230 V type AWB AWB AC...

Страница 5: ...point Do not dispose of component in domestic waste The work sequences for commissioning inspection and maintenance are summarised in the chapter Commissioning inspection and maintenance and are marke...

Страница 6: ...matched via inverter control The internal and external units are connected to each other hydraulically via the refrigerant lines Hydraulics The internal unit is equipped with a high efficiency HE cir...

Страница 7: ...he internal unit Liquid line Type AWB AWB AC Pipe 7 UNF thread 201 B04 6 mm Reducer x supplied 201 B05 to B13 10 mm 201 C10 to C16 10 mm Hot gas line 201 B04 12 mm Reducer x supplied 201 B05 to B13 16...

Страница 8: ...V e g for sensors 2 0 m BUS cable for internal external unit 12 V 2 5 m 1 5 m 43 V 2 5 m 1 5 m Recommended power cables Internal unit Type AWB AWB AC 201 B04 to B13 201 C10 to C16 Heat pump control u...

Страница 9: ...AWB AC 201 C10 201 C13 201 C16 Compressor Cable cross section 5 x 2 5 mm2 5 x 2 5 mm2 5 x 2 5 mm2 Max cable length 30 m 30 m 30 m Preparing for installation Requirements regarding on site connections...

Страница 10: ...into the lightning protec tion system Consider the heat emitted by the unit when planning your weatherproofing or an enclosure Condensate Ensure the condensate can drain freely and create a permanent...

Страница 11: ...ind cannot influence the fan area Strong wind can have a negative influence on the evaporator ventilation Take into account the lengths of the refrigerant lines See Connecting refrigerant lines Select...

Страница 12: ...00 A B A 500 500 500 A B A B 500 500 Fig 3 500 B 400 A B A 500 500 400 500 A B A B 500 500 C Fig 4 Single row layout 500 A 400 B A B A B 500 500 500 A B 500 A B 500 Fig 5 A Air intake B Air discharge...

Страница 13: ...echnical guide D KG conduit DN 100 only with entries below ground level E Rubber mounts supplied Note We recommend letting condensate drain away freely without condensate pipe Wall mounting Installati...

Страница 14: ...and free from the risk of frost Ensure ambient temperatures between 0 and 35 C Danger Dust gases and vapours can be damaging to health and trigger explosions Avoid dust gases and vapours in the instal...

Страница 15: ...gerant R410A In the following cases fit oil lift bends in the rising pipe In heating mode if the internal unit is installed higher than the external unit See diagram below In cooling mode if the inter...

Страница 16: ...unit exter nal unit 10 m 15 m 15 m 15 m 15 m 15 m Note No topping up is required for line lengths between 3 and 12 m Internal unit above external unit Internal unit below external unit or at same lev...

Страница 17: ...ines sepa rately B C A D Fig 12 Note Only for 230 Vappliances A Pipe bends for compensating vibrations B Tube clips with EPDM inserts C Line entry e g KG conduit with thermal insulation D Cables leads...

Страница 18: ...n Hold the pipe openings downwards or tempo rarily plug them Undo the nuts from connections C liquid line and D hot gas line of the refrigerant lines Type AWB AWB AC 201 B04 Slide the nuts onto the re...

Страница 19: ...0 Liquid line 7 10 mm UNF 33 to 42 Hot gas line 7 16 mm UNF 63 to 77 201 B13 Liquid line 7 10 mm UNF 33 to 42 Hot gas line 7 16 mm UNF 63 to 77 201 C10 Liquid line 7 10 mm UNF 33 to 42 Hot gas line 7...

Страница 20: ...g a shielding gas 3 Fit refrigerant lines and insulate them to provide protection from heat and vapour diffusion Tighten the nuts with the following torque Type AWB AWB AC Line Connection to inter nal...

Страница 21: ...iance To vent connect the hose to the air vent valve and route outwards Observe additional information regarding filling and venting See page 47 4 Thermally insulate pipes inside the building 5 Connec...

Страница 22: ...e as possible to the terminals and bundle tightly to the corresponding termi nals If 2 components are connected to the same terminal press both cores together in a single wire ferrule Danger In terms...

Страница 23: ...pe AWB AWB AC 201 B10 B13 201 C10 to C16 BUS cable 12 V Routing in the 230 V voltage area connection see page 34 B Type AWB AWB AC 201 B04 to B07 BUS cable 43 V Routing in the 230 V voltage area conne...

Страница 24: ...Switching module and power supply for instanta neous heating water heater See from page 37 C Power supply 230 V See page 34 F1 Fuse 6 3 A slow D Luster terminals See page 29 X1 Terminals for earth con...

Страница 25: ...valves for heating water buffer cylinder bypass in cool ing mode Connection values Max output 10 W Voltage 230 V Max switching current 4 2 A Connect the 3 way diverter valves for the bypass circuit i...

Страница 26: ...A1 HC1 Connection A to control unit Circulation pump C Without heating water buffer cylinder 211 2 Secondary pump With heating water buffer cylinder 212 2 Heating circuit pump A1 HC1 Connecting the te...

Страница 27: ...2 0 1 A 222 2 Switching mixer motor for external heat generator Signal mixer OPEN Connection values Output 10 W Voltage 230 V Max switching current 0 2 0 1 A 222 3 222 4 Control of external heat gene...

Страница 28: ...sXF Terminals Function Explanation 224 7 Circulation pump for DHW reheating or Connection values Max output 100 W Voltage 230 V Max switching current 4 2 A Control of the immersion heater EHE for con...

Страница 29: ...s soon as the contact opens The power OFF contact signal switches off the supply voltage to the relevant function components subject to power supply utility For the instantaneous heating water heater...

Страница 30: ...ure limiter to restrict the maxi mum temperature for underfloor heating systems in series see page 26 Secondary pump is connected at the factory Connect the temperature limiter on site 211 4 Connectio...

Страница 31: ...e KM BUS distributor accessories if several devices are connected KM BUS subscriber examples Extension kit mixer for heating circuit M2 HC2 Remote control Vitotrol 200A or Vitotrol 300B input the heat...

Страница 32: ...a the heat pump control unit A S DE 0 10V f A A DE D DE 5 6 3 4 1 2 1 2 B L1 N H L1 N M 1 C D F G E K Fig 24 A EA1 extension B Power supply 1 N PE 230 V 50 Hz C Junction box on site D Fuses and contac...

Страница 33: ...ge the BUS connection wires between the internal and external units Route the BUS connecting cable in the 230 V volt age area External unit Overview of connections Opening external unit wiring chamber...

Страница 34: ...orrect electrical installations can lead to seri ous injury from electrical current and result in appliance damage Connect the power supply and implement all safety measures e g RCD circuit in accord...

Страница 35: ...rol unit Connection to the same MCB fuse provides addi tional safety when the power is switched off Observe the power consumption of the connected consumers The PE wire of the power cable must be appr...

Страница 36: ...unit power supply 400 V Please note Incorrect phase sequence can cause damage to the appliance Make the compressor power supply only in the phase sequence specified see terminals with a clockwise rota...

Страница 37: ...F can be used Power supply with power OFF Without on site load disconnect The power OFF signal is connected directly to the heat pump control unit with heat pump cascades the con nection is only made...

Страница 38: ...open power OFF enabled feed TN C system H Economy tariff meter K Feed TN C system Power supply with power OFF With on site load disconnect The power OFF signal is connected to the on site con tactor o...

Страница 39: ...e control receiver contact open power OFF enabled with backup fuse H Economy tariff meter K Feed TN C system L Mains isolator Connecting the power OFF signal in heat pump cascades A B C D E G X3 7 X3...

Страница 40: ...tion with PV systems for on site power consumption H Bi directional meter for PV systems to consume power on site Energy taken from power supply utility and energy fed into power supply utility K Mete...

Страница 41: ...F function is integral to Smart Grid Therefore do not connect the power OFF signal to terminals X3 6 and X3 7 Do not remove jumper Closing the heat pump Please note If a casing door is not securely cl...

Страница 42: ...Fig 43 Note Ensure that the locking screws are tightened before operating Fitting side cover for external unit In reverse order to Opening external unit wiring cham ber See page 33 Installation seque...

Страница 43: ...e 48 10 Checking electrical connections of the internal unit for firm seating 11 Checking the free running of the fan in the external unit 49 12 Cleaning the external unit heat exchanger evaporator 49...

Страница 44: ...the equipotential bonding of the building Please note Commissioning immediately after installation can lead to appliance damage Wait at least 30 min between installing and commissioning the appliance...

Страница 45: ...ollution Before evacuating the refrigerant lines and the internal unit check all connections for tight ness with leak detection spray Keep the valves on the external unit shut and fill the system with...

Страница 46: ...12 m For lengths of refrigerant lines see page 16 Refrigerant R410A may only be topped up in a liquid state Danger Direct contact with refrigerant can cause skin damage Wear safety goggles and protec...

Страница 47: ...his type of refrigerant Danger Direct contact with refrigerant can be harmful to skin Wear safety goggles and protective gloves when working on the refrigerant circuit Check the connections for refrig...

Страница 48: ...unit panel into the service posi tion See page 61 6 Open the programming unit See page 60 A B Fig 46 7 To prevent damage to electrical components con nect an on site hose to secondary circuit air ven...

Страница 49: ...th the fans while they are operating can result in serious cutting injuries Isolate the external unit from the power supply and safeguard against reconnection Do not open the appliance until the fan h...

Страница 50: ...The refrigerant circuit must be checked for tightness See chapter Checking the refriger ant circuit for tightness The fill valves on the external unit must be open when the appliance is switched on S...

Страница 51: ...itch ON the ON OFF switch on the control unit The prompt Start commissioning appears auto matically on commissioning Note The commissioning assistant can also be started manually To do this press and...

Страница 52: ...wn OK simultaneously for approx 4 s Deactivating the service menu The service menu remains active until it is disabled with Terminate service or if no key is pressed for 30 min Setting parameters usin...

Страница 53: ...vice instructions System scheme Overview of all available system schemes Component System scheme 0 1 2 3 4 5 6 11 Heating circuit A1 HC1 X X X X M2 HC2 X X X X DHW cylinder X X X X Immersion heater 0...

Страница 54: ...sion kit mixer for heating circuit M2 HC2 System definition System scheme 7000 With heating circuit M2 HC2 Note Set rotary switch S1 in the extension kit to 2 See Mixer extension kit in stallation ins...

Страница 55: ...nd 730C External changeover of the operating status of various system components System definition System components for external changeover 7011 0 to 127 Operating status for external changeover 7012...

Страница 56: ...for DHW heating External heat source Enable external heat source for DHW heating 7B0D 1 Release circulation pump for DHW reheating External heat source Enable booster heaters for DHW heating 6014 1 P...

Страница 57: ...reshold for electrical power 7E04 0 to 300 0 to 30 kW Enable functions for utilisation of power generated on site Photovoltaics Enable own energy consumptn for set DHW temperature 2 7E10 1 Enable own...

Страница 58: ...pump in cascade 700C 0 to 15 Number of lag heat pumps 7029 1 to 4 Communication Enable LON communication module 7710 1 1 Number of heat pump in cascade 7707 1 to 4 LON system number 7798 1 to 5 1 to 5...

Страница 59: ...15 C e g during storage or transport the high limit safety cut out of the instantaneous heating water heater may respond Heat up the high limit safety cut out to above 20 C and press reset button on...

Страница 60: ...60 See from page 24 Opening the programming unit 1 3 2 2x Fig 50 Removing cover from programming unit if necessary 5 4 4x Fig 51 Maintenance Overview of electrical components 5700 542 GB Maintenance...

Страница 61: ...61 4x 1 3 2 Fig 52 Maintenance Placing the control panel in its service position 5700 542 GB Maintenance...

Страница 62: ...aneous heat ing water heater G Instantaneous heating water heater H Drain fill valve secondary circuit Overview of internal components External unit Danger Contact with live components can lead to ser...

Страница 63: ...porator OAT D Evaporator temperature sensor OMT E 4 way diverter valve F High pressure switch pHi G Compressor head temperature sensor CTT H Electronic expansion valve EEV K Temperature sensor refrige...

Страница 64: ...evaporator OAT D Evaporator temperature sensor OMT E 4 way diverter valve F Electronic expansion valve EEV G Compressor head temperature sensor CTT H High pressure switch pHi K Liquid separator L Tem...

Страница 65: ...ir intake evaporator OAT D Evaporator temperature sensor OMT E Temperature sensor refrigerant inlet evaporator OCT F 4 way diverter valve G Electronic expansion valve EEV H Liquid separator K High pre...

Страница 66: ...re sensor swimming pool F21 NTC 20 k Internal unit see page 62 Controller and sensor PCB see page 30 Flow temperature sensor secondary circuit F8 Return temperature sensor secondary circuit F9 Pt500A...

Страница 67: ...200 Resistance in k Fig 57 Other sensors 10 1 10 30 50 70 90 110 Temperature in C 0 4 0 6 0 8 2 4 6 8 20 Resistance in k Fig 58 Internal unit Viessmann NTC 20 k marked orange 80 120 160 200 Temperatu...

Страница 68: ...Resistance in Temperature in C 60 140 180 620 700 780 860 20 Fig 60 External unit NTC 10 k without ID 0 1 1 10 100 1000 Resistance in k 30 20 10 0 10 20 30 40 50 60 70 80 90 100 Temperature in C Fig 6...

Страница 69: ...located on the main PCB Fuse F101 is located on the AVI PCB Fuses F1 and F3 6 3 A slow H 250 V Max power loss 2 5 W Fuse F101 1 0 A slow L Max power loss 2 5 W Danger Removing the fuse does not switc...

Страница 70: ...ist Position number of the individual part within the assembly from this parts list D C B A Fig 63 A Type plate B Casing assembly internal unit C Electrical equipment assembly internal unit D Hydrauli...

Страница 71: ...e plate A on page 70 Position number of the part from this parts list Pos Part 0004 Touch up spray paint white 0005 Touch up paint stick white 0007 Vitocal 200 S installation and service instructions...

Страница 72: ...72 0001 0005 0006 0004 0002 0008 0003 0007 0008 0009 0009 0010 0009 Fig 64 Parts lists internal unit Internal unit casing 5700 542 GB Components...

Страница 73: ...l panel 0004 Contact guard 0005 Rear pipe outlet with gasket 0006 Front pipe outlet with gasket 0007 Screws set 0008 Viessmann logo 0009 Fixing clips 2 pce 0010 Wall mounting bracket Parts lists inter...

Страница 74: ...0017 0016 0021 0030 0004 0003 0031 0028 0010 0005 0029 0015 0018 0017 0001 0019 0020 0009 0007 0002 0026 0026 0012 0011 0008 0022 Fig 65 Parts lists internal unit Internal unit electrical equipment 5...

Страница 75: ...left right 0018 Fibre optic cable 0019 Connecting cable 4 pole length 85 mm 0020 Ribbon cable AWG 28 24 x 0 09 mm 0021 Cable trunking set 0022 Body bound rivet 0026 Fuse and mains power terminal 0028...

Страница 76: ...017 0002 0018 0024 0017 0017 0018 0024 0018 0018 0026 0022 0009 0010 0011 0012 0013 0014 0015 0019 0020 0021 0027 0011 0012 0023 0028 0022 0016 0006 0018 0025 0026 0016 0022 0022 0003 0016 0008 0010 F...

Страница 77: ...t gas line 0013 Union nut G with sealing cap for Schrader valve 0014 Soldered bush 10 x UNF 0015 Soldered bush 15 16 x UNF 0016 O ring 28 0 x 2 5 mm 0017 Gasket 21 x 30 x 2 0 mm 0018 Gasket 27 x 38 x...

Страница 78: ...0008 0009 0010 0011 0012 0013 0014 0018 0019 0020 0026 0011 0016 0017 0023 0017 0017 0017 0027 0010 0021 0025 0016 0017 0017 0024 0025 0021 0016 0015 0021 0015 0021 0029 0015 0021 0024 0001 0021 0028...

Страница 79: ...oldered bush 10 x UNF 0014 Soldered bush 15 16 x UNF 0015 O ring 28 0 x 2 5 mm 0016 Gasket 21 x 30 x 2 0 mm 0017 Gasket 27 x 38 x 2 0 mm 0018 Schrader valve 0019 Sealing cap 0020 Valve body 0021 Sprin...

Страница 80: ...80 Parts lists internal unit Hydraulics internal unit type AWB AC cont 5700 542 GB Components...

Страница 81: ...ils are required when ordering parts Serial no of external unit see type plate Position number of the part from this parts list Parts list external unit 230 V type AWB AWB AC 201 B04 Ordering parts 57...

Страница 82: ...006 0023 0027 0009 0014 0028 0026 0024 0021 0010 0022 0016 0002 0001 0003 0017 0032 0013 0018 0029 0007 0012 0011 Fig 68 Parts list external unit 230 V type AWB AWB AC 201 B04 Parts external unit 230...

Страница 83: ...Evaporator 0022 Joining plate 0023 Retaining bracket evaporator 0024 Top panel 0025 M5 nut 0026 Transport handle 0027 Side panel left 0028 Terminal strip 4 pole 0029 Electronic expansion valve 0030 Te...

Страница 84: ...84 Parts list external unit 230 V type AWB AWB AC 201 B04 Parts external unit 230 V type AWB AWB AC 201 B04 cont 5700 542 GB Components...

Страница 85: ...details are required when ordering parts Serial no see type plate Position number of the part from this parts list Parts list for external unit 230 V type AWB AWB AC 201 B05 B07 Ordering parts 5700 5...

Страница 86: ...0021 0022 0023 0012 0038 0020 0013 0019 0018 0010 0009 0002 0001 0008 0003 0037 0011 0005 0014 0015 0017 0016 0043 0042 0006 Fig 69 Parts list for external unit 230 V type AWB AWB AC 201 B05 B07 Part...

Страница 87: ...supply 0022 PCB mains filter 0023 Connection plate 0026 Evaporator 0027 Grille 0028 Retainer temperature sensor 0029 Transformer 0030 Partition wall 0031 Control unit 0032 Motor support 0033 Top panel...

Страница 88: ...88 Parts list for external unit 230 V type AWB AWB AC 201 B05 B07 Parts external unit 230 V type AWB AWB AC cont 5700 542 GB Components...

Страница 89: ...dividual part within the assembly from this parts list B C D A Fig 70 A Type plate B Casing assembly external unit C Electrical equipment assembly external unit D Hydraulic assembly external unit Part...

Страница 90: ...0007 0007 0005 0015 0015 0010 0010 0011 0011 0019 0018 0023 0021 0017 0014 0012 0013 0022 0001 Fig 71 Parts lists for external unit 230 V type AWB AWB AC 201 B10 B13 Casing external unit 230 V type AW...

Страница 91: ...Transport handle left 0014 Motor support 0015 Air inlet ring 0016 Transport handle right 0017 Control unit external unit 0018 Temperature sensor NTC 10 k OMT 0019 Temperature sensor NTC 10 k OAT 0020...

Страница 92: ...12 0011 0010 0009 0008 0007 0006 0001 0003 0002 0004 Fig 72 Parts lists for external unit 230 V type AWB AWB AC 201 B10 B13 Electrical equipment external unit 230 V type AWB AWB AC 201 B10 B13 5700 54...

Страница 93: ...0010 PCB retainer 0011 Cable retainer 0012 Strain relief 0013 Cable control unit power supply Parts not shown Pos Part 0014 Cable harness compressor 0015 Communication cable control unit inverter 001...

Страница 94: ...94 0006 0004 0002 0005 0010 0001 0003 0007 0008 Fig 73 Parts lists for external unit 230 V type AWB AWB AC 201 B10 B13 Hydraulics external unit 230 V type AWB AWB AC 201 B10 B13 5700 542 GB Components...

Страница 95: ...alve hot gas line 0006 Oil separator 0007 Electronic expansion valve 0008 Compressor thermal insulation 0010 Shut off valve liquid line Parts not shown Pos Part 0009 Temperature sensor NTC 50 k CTT Pa...

Страница 96: ...96 Parts lists for external unit 230 V type AWB AWB AC 201 B10 B13 Hydraulics external unit 230 V type cont 5700 542 GB Components...

Страница 97: ...vidual part within the assembly from this parts list B C D A Fig 74 A Type plate B Casing assembly external unit C Electrical equipment assembly external unit D Hydraulic assembly external unit Parts...

Страница 98: ...0005 0015 0015 0007 0007 0010 0010 0011 0011 0006 0016 0020 0002 0004 0003 0018 0014 0012 0013 Fig 75 Parts lists external unit 400 V type AWB AWB AC 201 C10 C13 C16 Casing external unit 400 V type AW...

Страница 99: ...grille left 0013 Transport handle left 0014 Motor support 0015 Air inlet ring 0016 Transport handle right 0017 Control unit external unit 0018 Temperature sensor NTC 10 k OMT 0019 Temperature sensor...

Страница 100: ...0003 0002 0007 0008 0009 0012 0017 0010 0011 0001 Fig 76 Parts lists external unit 400 V type AWB AWB AC 201 C10 C13 C16 Electrical equipment external unit 400 V type AWB AWB AC 201 C10 C13 C16 5700...

Страница 101: ...power supply Parts not shown Pos Part 0013 Cable harness compressor 0014 Cable harness complete compressor 0015 Communication cable drivers 0016 Communication cable internal unit 0018 Connecting cabl...

Страница 102: ...002 0008 0008 0009 0011 0001 0005 0010 0006 0003 0007 Fig 77 Parts lists external unit 400 V type AWB AWB AC 201 C10 C13 C16 Hydraulics external unit 400 V type AWB AWB AC 201 C10 C13 C16 5700 542 GB...

Страница 103: ...hot gas line 0006 Oil separator 0007 Electronic expansion valve 0008 Compressor thermal insulation 0009 Temperature sensor NTC 50 k CTT 0010 Shut off valve liquid line 0011 Compressor power supply cov...

Страница 104: ...the following conditions Room temperature C Outside temperature C Temperature Cylinder temp top con stant Yes 1 K Secondary circuit flow temperature C Rising From Open From Open Temperature different...

Страница 105: ...tion Commission ing Maintenance Service Enable compressor 5000 1 Enable use of compressor stage 5012 15 Output compressor stage 5030 Rated heating output according to type plate Primary source output...

Страница 106: ...DHW after high pres sure shutdown 6017 1 Electric booster heater Parameters Code Delivered condition Commission ing Maintenance service Enable instantaneous heating water heater 7900 1 Enable electri...

Страница 107: ...ote control 2003 0 Heating curve level 2006 0 0 K Heating curve slope 2007 6 0 6 Influence room temperature hook up 200 A 10 Room temperature hook up 200 B 0 Max flow temperature heating circuit 200E...

Страница 108: ...ter bank electric 7D01 0 Enable reheater bank hydraulic 7D02 0 Enable humidity sensor 7D05 0 Enable CO2 sensor 7D06 0 Set extract air temperature 7D08 200 20 C Flow rate reduced ventilation 7D0A 120 m...

Страница 109: ...ature PV 7E23 0 0 K Reduce set room temperature PV 7E25 0 0 K Smart Grid Parameter Code Delivered condition Commission ing Maintenance Service Enable Smart Grid 7E80 0 Smart Grid Enable elec heat 7E82...

Страница 110: ...r 7779 0 LON system number 7798 1 Interval for data transfer via LON 779C 20 min Source outside temperature 77FC 0 Send outside temperature 77FD 0 Source time 77FE 0 Send time 77FF 0 Control Parameter...

Страница 111: ...ng output data to EN 14511 A 7 W35 Rated heating output kW 3 20 4 60 6 60 8 72 9 14 Power consumption kW 1 27 1 74 2 68 3 46 3 70 Coefficient of performance COP in heating mode 2 58 2 64 2 49 2 55 2 4...

Страница 112: ...sor with stalled armature A 20 25 25 25 32 MCB fuse protection A 16 16 16 20 32 IP rating IP X4 X4 X4 X4 X4 Internal unit electrical values Heat pump control unit PCB Rated voltage control unit PCB 1...

Страница 113: ...idth mm 869 1040 1040 975 975 Total height mm 610 865 865 1255 1255 Internal unit dimensions Total length mm 360 360 360 360 360 Total width mm 450 450 450 450 450 Total height mm 905 905 905 905 905...

Страница 114: ...performance COP in heating mode 3 79 3 72 3 20 Output control kW 2 73 to 10 92 3 30 to 12 29 Heating output data to EN 14511 A7 W35 5 K spread Rated heating output kW 10 16 12 07 15 5 Fan speed rpm 6...

Страница 115: ...pressure drop RFH at minimum flow rate mbar 450 450 450 kPa 45 45 45 Max flow temperature C 55 55 55 External unit electrical values Rated voltage compressor 3 N PE 400 V 50 Hz Max operating current c...

Страница 116: ...30 m g m 60 60 60 Compressor hermetically sealed Type Double rotating pis ton Double rotating pis ton Double rotating pis ton Permiss operating pressure High pressure side bar MPa 43 4 3 43 4 3 43 4...

Страница 117: ...nal unit UNF Max line length liquid line hot gas line m 30 30 30 Sound power of external unit at rated heating output Measurements with reference to EN 12102 EN ISO 9614 2 Weighted total sound power l...

Страница 118: ...ponents for PV system fully installed optional Preferred appointment 1 Date Time 2 Date Time The work that is requested to be carried out by Viessmann will be billed in accordance with the latest Vies...

Страница 119: ...2 35 In accordance with the following Directives this product is designated with _ 97 23 EC 2009 125 EC 2 2004 108 EC 2010 30 EU 2 2006 95 EC 811 2013 2 2011 65 EU 813 2013 2 Details according to the...

Страница 120: ...ds 17 Capacity data cooling 111 114 Casing assembly Internal unit 72 Casing parts Internal unit 72 Casing spare parts Internal unit 72 Charging Refrigerant circuit 46 Checking Fuses 69 Sensors 66 Chec...

Страница 121: ...External heat source 56 External unit Cable lengths 8 Checking electrical connections 50 Cleaning 49 Closing 42 Dimensions 113 116 Electrical connection 33 Electrical values 112 115 Fill valve 45 46...

Страница 122: ...le 8 Power supply 37 Specification 112 115 Instructing the system user 59 Intended use 5 Interface internal unit external unit 33 Interface PCB 33 Internal external unit connecting cable 33 Internal c...

Страница 123: ...External unit type AWB AWB AC 201 B10 B13 92 External unit type AWB AWB AC 201 C10 C13 C16 100 Internal unit 74 Parts external unit 81 Parts hydraulic External unit type AWB AWB AC 201 B10 B13 94 Exte...

Страница 124: ...AWB AC 201 B10 B13 89 External unit type AWB AWB AC 201 C10 C13 C16 97 Spare parts casing External unit type AWB AWB AC 201 B10 B13 90 External unit type AWB AWB AC 201 C10 C13 C16 98 Spare parts elec...

Страница 125: ...loor heating circuit 26 Union nuts replacing 18 Use 5 Utilisation of power generated on site 35 V Vacuum gauge 45 Vacuum meter 46 Vacuum pump 45 46 Ventilation 56 Venting 47 Vibration isolation 10 17...

Страница 126: ...126 5700 542 GB...

Страница 127: ...127 5700 542 GB...

Страница 128: ...54825 7560794 7560795 Viessmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendor...

Отзывы: