10
0
9.
Check that the level switch and
overflow alarm switch are posi-
tioned correctly. Both must be fully
inserted into the locking ring fitting,
so that they rest against the lock-
ing ring fitting.
10.
Carry out a visual inspection of all
components for damage and leaks.
11.
Close the condensate lifting sys-
tem cover again.
12.
Restart the condensate lifting sys-
tem.
13.
Record service on page 13.
Maintenance
(cont.)
5601325