System characteristics

Cause

Measure

Container overflowing or fault
message triggered by overflow
alarm switch (if installed)

■ No voltage at power

supply

■ Check power sup-

ply

■ Filter basket contami-

nated

■ Non-return valve con-

taminated

■ Clean component,

replace if required

■ Fuse in the control unit

blown

■ Level switch faulty.
■ Pump faulty

Replace component

■ The switching point of

the level switch or
overflow alarm switch
is too high (air pocket
in pressure tube may
have escaped).

■ Remove switch

briefly to vent the
pressure tube

■ Condensate supply

volume exceeds the
system output

■ Check the pump

rate by means of
volumetric measur-
ing, if required in-
stall a larger or ad-
ditional condensate
lifting system

■ Delivery head at drain

too large

■ Check pump rate or

delivery head

Feed pump starts repeatedly
even though no condensate is
flowing

■ Non-return valve is

contaminated or dam-
aged (causing conden-
sate return)

■ Drain and undo the

drain hose. Remove
non-return valve
with a pair of poin-
ted pliers and clean,
replace if required

!

Please note

The feed pump is equipped with an automatically resetting temperature lim-
iter. The feed pump motor is switched off in the event of overheating and
starts again automatically when it has cooled down sufficiently.
The cause for overheating must be remedied. Further operation without
remedying the cause leads to the destruction of the temperature limiter and
pump motor damage.

 

Troubleshooting

5601325

 

Содержание 7441 770

Страница 1: ...st the risk of material losses and envi ronmental pollution Note Details identified by the word Note contain additional information Target group These instructions are exclusively intended for qualified contractors Work on electrical equipment may only be carried out by a qualified electrician Regulations to be observed National installation regulations Statutory regulations for the preven tion of...

Страница 2: ...e appli ance and let it cool down Do not touch hot surfaces on the appliance fittings or pipe work Please note Electronic assemblies can be damaged by electrostatic dis charge Prior to commencing work touch earthed objects such as heating or water pipes to dis charge static loads Repair work Please note Repairing components that fulfil a safety function can compro mise the safe operation of the sy...

Страница 3: ...t operation The condensate removal pump is not suitable for pumping the following liq uids Non neutralised condensate from oil condensing boilers Salt water Water containing chlorine Condensate with textile or paper par ticles Aggressive liquids chemicals Corrosive flammable explosive and gas emitting liquids Spare parts lists Information about spare parts can be found at www viessmann com etapp o...

Страница 4: ... horizontal level and load bearing installation surface Easy accessibility for maintenance work Available socket 230 V 50 Hz per manent voltage in the immediate vicinity The length of the power cable is 2 m Existing sewer connection min DN 40 This must allow drainage of min 18 l min without obstruction Note Choose an installation location that means the supply and drain hoses are as short as possi...

Страница 5: ...on densate lifting system with a fall Secure the hose with hose clips Note Never step on the hose Protect the hose against mechanical damage 5 Route the drain hose into the drain age system Secure the hose with hose clips Note Secure the free end of the drain hose because water flows out under pressure If the drain hose is extended and or constricted by hose con nectors this leads to a reduction i...

Страница 6: ...6 Note The level switch and overflow alarm switch must be fully inserted into the locking ring fitting so that they rest against the locking ring fitting Positioning and connecting cont 5601325 ...

Страница 7: ...9 1 3 M 1 BU BN GNYE A B L N A Power supply 230 V 50 Hz B Feed pump 230 V 50 Hz Colour coding to DIN IEC 60757 BN brown BU blue GNYE green yellow Terminal assignment of the overflow alarm switch Note If required connect the overflow alarm switch with the sockets supplied in the cap 1 2 3 Breaking capacity 250 V 6 A resistive load Electrical connection Flat pin sockets 6 3 x 0 8 mm Electrical conne...

Страница 8: ...y subject to the volume and contamination of the condensate but at least once a year It must be carried out by an approved heating contractor or personnel trained by this approved heating contractor Inspection 1 Open the condensate lifting system cover 2 Check filter basket for contamina tion and clean if required 3 Check that the hoses are secure 4 Check that the level switch and overflow alarm s...

Страница 9: ...ination inside the pump Open pump cover and clean pump Then carefully clean the sealing faces refit the pump cover cor rectly pressure chamber above the pressure joint and secure with screws Note First screw in the two fixing screws next to the pressure joint and tighten then the ones opposite Then screw in and tighten all other fixing screws Please note Leaks in the pump cover lead to reduced out...

Страница 10: ...serted into the locking ring fitting so that they rest against the lock ing ring fitting 10 Carry out a visual inspection of all components for damage and leaks 11 Close the condensate lifting sys tem cover again 12 Restart the condensate lifting sys tem 13 Record service on page 13 Maintenance cont 5601325 ...

Страница 11: ...ic measur ing if required in stall a larger or ad ditional condensate lifting system Delivery head at drain too large Check pump rate or delivery head Feed pump starts repeatedly even though no condensate is flowing Non return valve is contaminated or dam aged causing conden sate return Drain and undo the drain hose Remove non return valve with a pair of poin ted pliers and clean replace if requir...

Страница 12: ...eat generator It switches when the con densate level is approx 150 mm and is reset when the level is approx 135 mm The alarm delay available as an accessory for connection to the over flow alarm switch enables the heat gen erator to be switched off in parallel to a fault message or after a time delay A delayed heat generator shutdown can only be carried out if condensate flow ing back cannot cause...

Страница 13: ...e service Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Report 5601325 ...

Страница 14: ... Max delivery head m 5 5 Pump rate With 4 m delivery head l h 300 Max l h 660 Condensate temperature ºC 5 60 Ambient temperature ºC 5 40 Weight In the delivered condition kg 8 Curve of the feed pump with a hose length of 6 m 4 0 1 2 3 0 100 200 300 400 500 5 6 600 700 Flow rate l h Delivery head m Specification 5601325 ...

Страница 15: ...of the components in domestic waste Note Information about collection points for this product can be obtained from the local council the public waste disposal authority an authorised body for the disposal of electrical and electronic products or the rubbish collection serv ice Final decommissioning and disposal 5601325 ...

Страница 16: ...16 Declaration of Conformity 5601325 ...

Страница 17: ...17 5601325 ...

Страница 18: ...18 5601325 ...

Страница 19: ...19 5601325 ...

Страница 20: ... Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 5601325 Subject to technical modifications ...

Отзывы: