-17-
Connecting Electric Lock
Door Lock Controlled with Internal Power
Door Lock Controlled with Dry Contact
1.Electronic lock of Power-on-to-unlock
type should be used.
2.The door lock is limited to 12V, and hold-
ing current must be less than 250mA.
3.The jumper should be placed on position
2 and 3 before connecting.
4.The door lock control is not timed from
Exit Button(EB).
5.The
Unlock Mode
must be set to 0 (by
default).
1.The external power supply must be used
according to the lock.
2.The inside relay contact is restricted to
230Vac 1A or 24Vdc 1A.
3.The jumper must be taken off before
connecting.
4.Setup the
Unlock Mode
according to
different lock types.
• Power-on-to-unlock type:Unlock
Mode=0 (by default)
• Power-off-to-unlock type:Unlock
Mode=1
EB
*
LOCK
Jumper position on 2&3
1 2 3
L1 L2 PL S+ S-
Take off the jumper
1 2 3
L1 L2 PL S+ S-
LOCK
POWER
SUPPLY
WIRING
B5
relay actuator is needed for 2nd lock connection.
-18-
WIRING
• Max.4 door stations can be connected to the system.
•
Connecting Basic One-to-one
Connecting Multi Door Stations
with module M-SM4
BUS(IM) BUS(DS)
-
+
L1 L2 PL S+ S-
ID=0
Code=
00
, DIP6=on
1 2 3 4 5 6
ON
DIP
L2
L1
DIP Switches
RF CARD
P
26
/
40
AC~
100~240VAC
100~240VAC
M-SM4
A B C D
OFF
ON
Impedance
switch
BUS(IM) BUS(DS)
P26
/
40
AC~
ID=0
1
st
door station
ID=1
2
nd
door station
ID=2
3
rd
door station
ID=3
4
th
door station
L1 L2 PL S+ S-
L1 L2 PL S+ S-
L1 L2 PL S+ S-
L1 L2 PL S+ S-
RF CARD
RF CARD
RF CARD
RF CARD
• The door station work in Standard mode in this situation. Refer to Page 9 in detail.
• The door station is also compatible with other monitors which are provided by our company.
Take off the jumper
1 2 3
L1 L2 PL S+ S-
POWER
SUPPLY
MAGLOCK
2
Code=
00
, DIP6=on
If more than one door station is connected to one house, each
should have a different
address 0, 1, 2, or 3.
Refer to Page 8 for more details
about the address setting of door stations
.