19
XTO-IP
Alarm panel
INSTALLATION MANUAL
4. TRANSMITTED EVENTS LIST
The XTO-iP panel can be configured to enable or disable the
transmission of events like alarms or defaults.
The installer can modify the default sending settings for those
events, although it will end the EN50131 standard compliance.
How to modify the transmission state
•
At initial programming, right after the PERIODIC TEST CALL step:
•
After initial programming, using a remote keypad :
Example :
If the monitoring station system is set to receive arms and disarms, the
ARM / DISARM
parameter must be
changed from
NOT TRANSMITTED
to
ALARM / END
.
Press
OK or YES
to access
EVENT TRANS. MODIFICATION
menu.
CODE/STATE
MODIFICATION
Use the arrows
to access :
CONFIGURATION
(level 4) >
CONFIGURATION MONITOR. STATION
>
MONITORING PARAMETERS
>
EVENT TRANS. MODIFICATION
Then use the arrows
to determine the event to modify. Press
OK or YES
to edit.
These are the default transmitted events :
DEVICE
(intrusions)
ALERT
(Panic Buttons)
PANEL LOW BATT.
TAMPER
DEVICE LOW BATT.
PERIODIC TEST
DURESS CODE
FIRE
MEDICAL ASSIST.
ETHERNET CABLE
AC POWER LOSS
(AC Power supply)
The following events are not sent by default :
PANEL RESET
PHONELINE FAULT
RADIO JAMMING
SUPERVISION
5 WRONG CODES
ALARM CANCEL
ARM/DISARM
(On/Off)
ZONE BYPASS
(bypass function enabling/dsiabling)
SWINGER SHUTDOWN
There is 3 different transmission states :
ALARM
: event transmitted upon occurrence
ALARM/END :
event is transmitted on occurrence and on event restoral
NOT TRANSMITTED :
event is not transmitted, however it will appear on the keypad.