Victron energy VBC-HV Скачать руководство пользователя страница 6

 

1.4 

How does the VE.Net Battery Controller work? 

The capacity of a battery is rated in Amp hours (Ah). For example, a 
battery that can deliver a current of 5 Amps for a period of 20 hours is 
rated at 100 Ah (5 * 20 = 100). The VBC-HV continuously measures the 
net current flow into or out of the battery. This way it can calculate the 
amount of energy removed from or added to the battery. But since battery 
age, discharge current and temperature all influence 

the battery‟s 

capacity; you cannot rely simply on an Amp hours reading. When the 
same 100 Ah battery is discharged completely in two hours, it may only 
give you 56 Ah (because of the higher rate of discharge). 
 
As you can see the battery‟s capacity is almost halved. This phenomenon 
is called Peukert efficiency (see chapter 4.1.2). Also, when the 
temperature of the battery is low, its capacity is decreased even more. 
This is why simple Amp hour counters or Voltmeters give you far from an 
accurate state-of-charge indication. 
 
The VBC-HV can display both the Amp hours removed (not 
compensated) and the actual state of charge (compensated by Peukert 
efficiency and charge efficiency). Reading the state-of-charge is the best 
way to read your battery. This parameter is shown as a percentage, 
where 100% represents a fully charged battery and 0% represents a 
completely flat battery. You can compare this with a fuel-gauge in a car. 
 
The VBC-HV also makes an estimation of how long the battery can 
support the present load (time to go readout). This is actually the time left 
until the battery needs to be charged again. If the battery load is 
fluctuating heavily it is best not to rely on this reading too much since it is 
a momentary readout and must be used as a guideline only. We always 
encourage the use of the state-of-charge readout for accurate battery 
monitoring. 

Содержание VBC-HV

Страница 1: ...Manual EN VE Net Battery Controller 70 385V model VBC HV...

Страница 2: ......

Страница 3: ...PRODUCTS AND MAKES SUCH VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN AS IS BASIS IN NO EVENT SHALL VICTRON ENERGY B V BE LIABLE TO ANYONE FOR SPECIAL COLLATERAL INCIDENTAL OR CONSEQUENTIAL DAMAGES I...

Страница 4: ......

Страница 5: ...mpatible devices to communicate with each other This means that the charger for example can get information from the battery monitor to optimize the charge current It is possible to control and monito...

Страница 6: ...of the battery is low its capacity is decreased even more This is why simple Amp hour counters or Voltmeters give you far from an accurate state of charge indication The VBC HV can display both the A...

Страница 7: ...a short circuit and possibly an explosion 5 Remove personal metal items such as rings bracelets necklaces and watches when working with a battery A battery can produce a short circuit current high eno...

Страница 8: ...ller to a VE Net Panel or other VE Net device using a standard straight Cat5 cable The total length of Cat5 cables used in a VE Net network should not exceed 100m After installation and checking all t...

Страница 9: ...Net I T T GND VBC Battery system Relay connection Fuse 100mAT Temperature sensor Battery Vin max 385V VE Net Vin max 70V Figure 1 Battery negative System ground Battery positive Load Read the Safety...

Страница 10: ...chapter 4 1 3 for more information 3 2 Main menu To view more detailed information press the Enter button to enter the Battery Controller menu Name Description Units Battery voltage Displays the volta...

Страница 11: ...hes 100 again Amp hours Average discharge The average discharge over all the cycles counted Amp hours Number of cycles Every time the battery is discharged below 65 of its rated capacity and charged b...

Страница 12: ...uch batteries do not exist and a setting of 1 00 in the VBC HV is only implemented to bypass Peukert compensation The default setting for the Peukert exponent is 1 25 and is an acceptable average valu...

Страница 13: ...for a 12 V battery or 21 V for a 24 V battery A calculation example is shown below A 200 Ah battery is discharged with a constant current of 20 A and after 8 5 hours 1 75 V cell is reached So 20 h ra...

Страница 14: ...charging your battery not only keeps it in sync with the VBC HV but also prevents substantial capacity loss of your battery which limits its lifetime 4 1 4 Synchronisation parameters Based on increas...

Страница 15: ...current If the charge current is below this percentage of the battery capacity the battery can be considered as fully charged 4 1 10 1 Sync time The minimum time that the above two parameters must be...

Страница 16: ...the shunt at the maximum rated current 50 mV 1 100 1 Current offset Used to compensate for small errors in current measurement caused by unwanted offsets picked up by the measurement cables 0 A 60000...

Страница 17: ...arm 50 0 100 1 Low SOC clr The state of charge threshold that has to be reached to cancel an active state of charge alarm 80 0 100 1 Low SOC action The type of action to take when the alarm condition...

Страница 18: ...Supply current relay inactive 144V 5mA 288V 5mA Operating temperature range 0 50 C Potential free alarm contact Mode Normally open Rating 30V 3A max Dimensions VBC HV Housing 75 x 110 x 23mm 230x140x...

Страница 19: ......

Страница 20: ...n 06 Date 5 March 2010 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 Customer support desk 31 0 36 535 97 03 Fax 31 0 36 535...

Отзывы: