Step 3.)
Press “Enter” to enter the “Setup
alarms” menu.
Note:
If you can no
t find the “Setup alarms” menu, make sure that your
VPN is in
“user and install” mode.
4.3.2
Alarm options explained
Setup alarms
Name
Description
Default
Value
Rang
e
Step
size
Low
voltage
The battery voltage has to be below this threshold to
trigger the low voltage alarm.
126 V
96-384
0.1
Low
voltage clr
The threshold that has to be reached again to cancel
an active low voltage alarm.
126 V
96-384
0.1
Low volt.
action
The type of action to take when the alarm condition is
met.
None
None,
Relay,
Panel,
Both
High
voltage
The battery voltage has to be above this threshold to
trigger the high voltage alarm.
192 V
96-384
0.1
High
voltage clr
The threshold that has to be reached again to cancel
an active high voltage alarm.
192 V
96-384
0.1
High volt.
action
The type of action to take when the alarm condition is
met.
None
None,
Relay,
Panel,
Both
Low SOC
The low state of charge threshold that will activate the
alarm.
50 %
0-100
1
Low SOC
clr
The state of charge threshold that has to be reached to
cancel an active state of charge alarm.
80 %
0-100
1
Low SOC
action
The type of action to take when the alarm condition is
met.
None
None,
Relay,
Panel,
Both
Low current
The level below which a low current alarm will be
triggered.
-100 A
-30000
– 0
5
Low current
clr.
The level above which a low current alarm will be
cleared.
-90 A
-30000
– 0
5
Low current
action
The type of action to take when a low current alarm is
active.
None
None,
Relay,
Panel,
Both
High
current
The level above which a high current alarm will be
triggered.
100
0
–
30000
5
High
current clr
The level below which a high current alarm will be
cleared.
90
0
–
30000
5
High cur.
action
The type of action to take when a high current alarm is
active.
None
None,
Relay,
Panel,
Both
Enable
delay
The amount of time an alarm condition must be present
in order to trigger the alarm.
0 s
0
– 255
1
Disable
delay
The amount of time an alarm clear condition must be
present in order to disable the alarm.
0 s
0
– 255
1
Min. enable
time
The minimum amount of time the relay may remain
closed once an alarm condition has occurred.
0 min
0
– 255
1
Setup alarms
[Press Enter]