11
4.2
General settings
4.2.1
Where to find the “Setup monitor” menu
Step1)
Press “Enter” to enter the VBC-HV
menu.
Step 2)
Press “▼” to scroll through the
menu until you see “Setup
controller”.
Step 3)
Press “Enter” to enter the “Setup
monitor
“menu.
Note:
If you can‟t find the “Setup monitor” menu, make sure that your
VE.Net Panel is in
“user and install” mode.
4.2.2
Setup parameters explained:
Setup monitor
Name
Description
Default
Value
Range
Step
size
Battery capacity
The battery capacity in amp hours (Ah) at a 20h
discharge rate.
200 Ah
20-
65535
5
Sync. voltage
The battery controller considers the battery as
fully charged if the voltage is above this level.
158.4 V
96-384
0.1
Sync. current
If the charge current is below this percentage of
the battery capacity, the battery can be
considered as fully charged.
4 %
1-10
1
Sync. time
The minimum time that the above two
parameters must be met to consider the battery
as fully charged.
4 min
1-4
1
Bat. temperature
If the connection to the temperature sensor is
lost, this value is used in the calculations.
20 °C
0-50
1
Resync. to 100%?
Resets the state of charge manually to 100%.
Device name
The name of the battery controller that is used
in the VE.Net Panel.
Battery
Monitor
The settings on the advanced menu allow fine control of the battery
monitoring calculations performed by the VBC-HV. The default values
are suitable for most battery systems, so do not adjust these settings
without fully understanding the consequences.
Setup controller
[Press enter]
Battery voltage
157.40V
Battery Monitor
157V 0.0A 100%