5 h rating 
 
 
 
 
 
20 h rating, 

1.26

5

log

15

log

5

log

20

log

 

exponent,

Peukert 

n

 

 
 
When no ratings are given at all, you can measure your battery using a 
„constant load bank‟. In this way a second rating can be obtained, 
together with the 20 h rating which represents the rated battery capacity 
in most cases. This second rating can be determined by discharging a 
fully charged battery with a constant current; until the battery reaches 
1.75 V per cell (which is 10.5 V for a 12 V battery or 21 V for a 24 V 
battery). A calculation example is shown below: 
 
A 200 Ah battery is discharged with a constant current of 20 A and after 
8.5 hours 1.75 V/cell is reached. 
 
So, 
 
 
20 h rating, 
 
 
 
 
 

1.23

10

log

20

log

5

.

8

log

20

log

 

exponent,

Peukert 

n

 

 
A Peukert calculator is available at 

www.victronenergy.com

. 

4.1.3 

Synchronising the VBC-HV 

For a reliable readout of the state of charge of your battery, the battery 
monitor has to be synchronised regularly with the battery and charger. 

A

h

Ah

I

h

t

Ah

C

h r

15

5

75

5

75

1

1

5

A

h

Ah

I

h

Ah

C

h r

5

20

100

20

t

capacity)

 

(rated

 

100

2

2

2 0

A

I

h

t

20

5

.

8

1

1

A

h

Ah

I

h

t

Ah

C

h

10

20

200

20

200

2

2

2 0

Содержание VBC-HV

Страница 1: ...Manual EN VE Net Battery Controller 70 385V model VBC HV...

Страница 2: ......

Страница 3: ...PRODUCTS AND MAKES SUCH VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN AS IS BASIS IN NO EVENT SHALL VICTRON ENERGY B V BE LIABLE TO ANYONE FOR SPECIAL COLLATERAL INCIDENTAL OR CONSEQUENTIAL DAMAGES I...

Страница 4: ......

Страница 5: ...mpatible devices to communicate with each other This means that the charger for example can get information from the battery monitor to optimize the charge current It is possible to control and monito...

Страница 6: ...of the battery is low its capacity is decreased even more This is why simple Amp hour counters or Voltmeters give you far from an accurate state of charge indication The VBC HV can display both the A...

Страница 7: ...a short circuit and possibly an explosion 5 Remove personal metal items such as rings bracelets necklaces and watches when working with a battery A battery can produce a short circuit current high eno...

Страница 8: ...ller to a VE Net Panel or other VE Net device using a standard straight Cat5 cable The total length of Cat5 cables used in a VE Net network should not exceed 100m After installation and checking all t...

Страница 9: ...Net I T T GND VBC Battery system Relay connection Fuse 100mAT Temperature sensor Battery Vin max 385V VE Net Vin max 70V Figure 1 Battery negative System ground Battery positive Load Read the Safety...

Страница 10: ...chapter 4 1 3 for more information 3 2 Main menu To view more detailed information press the Enter button to enter the Battery Controller menu Name Description Units Battery voltage Displays the volta...

Страница 11: ...hes 100 again Amp hours Average discharge The average discharge over all the cycles counted Amp hours Number of cycles Every time the battery is discharged below 65 of its rated capacity and charged b...

Страница 12: ...uch batteries do not exist and a setting of 1 00 in the VBC HV is only implemented to bypass Peukert compensation The default setting for the Peukert exponent is 1 25 and is an acceptable average valu...

Страница 13: ...for a 12 V battery or 21 V for a 24 V battery A calculation example is shown below A 200 Ah battery is discharged with a constant current of 20 A and after 8 5 hours 1 75 V cell is reached So 20 h ra...

Страница 14: ...charging your battery not only keeps it in sync with the VBC HV but also prevents substantial capacity loss of your battery which limits its lifetime 4 1 4 Synchronisation parameters Based on increas...

Страница 15: ...current If the charge current is below this percentage of the battery capacity the battery can be considered as fully charged 4 1 10 1 Sync time The minimum time that the above two parameters must be...

Страница 16: ...the shunt at the maximum rated current 50 mV 1 100 1 Current offset Used to compensate for small errors in current measurement caused by unwanted offsets picked up by the measurement cables 0 A 60000...

Страница 17: ...arm 50 0 100 1 Low SOC clr The state of charge threshold that has to be reached to cancel an active state of charge alarm 80 0 100 1 Low SOC action The type of action to take when the alarm condition...

Страница 18: ...Supply current relay inactive 144V 5mA 288V 5mA Operating temperature range 0 50 C Potential free alarm contact Mode Normally open Rating 30V 3A max Dimensions VBC HV Housing 75 x 110 x 23mm 230x140x...

Страница 19: ......

Страница 20: ...n 06 Date 5 March 2010 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 Customer support desk 31 0 36 535 97 03 Fax 31 0 36 535...

Отзывы: