5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers
(L2, L3)
. These settings are imposed on the whole system by the
leader
L1
. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages
(not relevant for L2, L3)
ds8-ds7
Absorption
voltage
Float
voltage
Storage
voltage
Suitable for
off off
14.1
28.2
56.4
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
off on
14.4
28.8
57.6
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
on off
14.7
29.4
58.8
13.8
27.6
55.2
13.2
26.4
52.8
AGM Victron Deep Discharge
Tubular plate (OPzS) batteries in
semi-float mode
AGM spiral cell
on on
15.0
30.0
60.0
13.8
27.6
55.2
13.2
26.4
52.8
Tubular plate (OPzS) batteries in
cyclic mode
ds6: absorption time 8 or 4 hours
(not relevant for L2, L3)
on = 8 hours
off = 4 hours
ds5: adaptive charging characteristic
(not relevant for L2, L3)
on = active
off = inactive (fixed absorption time)
ds4: dynamic current limiter
on = active
off = inactive
ds3: UPS function
on = active
off = inactive
ds2: converter voltage
on = 230V / 120V off = 240V / 115V
ds1: converter frequency
(not relevant for L2, L3)
on = 50Hz
off = 60Hz
(the wide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to
‘off’ and do not reflect the actual settings in the microprocessor).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
DS-8
off
DS-7
off
DS-6
on
DS-5
on
DS-4
off
DS-3
off
DS-2
on
DS-1
on
DS-8
on
DS-7
off
DS-6
on
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
on
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230V
1 Frequency: 50Hz
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Absorption time: 8 h
5 Adaptive charging: on
4 Dyn. current limit: off
3 UPS function: off
2 Voltage: 230V
1 Frequency: 50Hz
Step 2
Example 3:
8, 7 AGM 14,7V
6 Absorption time: 8 h
5 Adaptive charging: on
4 Dyn. current limit: on
3 UPS function: off
2 Voltage: 240V
1 Frequency: 50Hz
Step 2
Example 4:
8, 7 Tubular-plate 15V
6 Absorption time: 4 h
5 Fixed absorption time
4 Dyn. current limit: off
3 UPS function: on
2 Voltage: 240V
1 Frequency: 60Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (lower button to the right of
the DIP switches).
The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the ’other settings’ can always be recovered.
Содержание Quattro 24
Страница 2: ......
Страница 4: ......
Страница 58: ......
Страница 114: ......
Страница 161: ...19 EN NL FR DE ES SE Appendix Er ro r float Err or Ob temperatur ...
Страница 171: ...29 EN NL FR DE ES SE Appendix Er ro r float Err or Ob temperatur ...
Страница 190: ......
Страница 191: ...1 EN NL FR DE ES SE Appendix APPENDIX A Overview connections ...
Страница 196: ...6 APPENDIX C Parallel connection ...
Страница 197: ...7 EN NL FR DE ES SE Appendix APPENDIX D Three phase connection ...
Страница 200: ...10 APPENDIX G Dimensions ...
Страница 201: ......
Страница 202: ......
Страница 203: ......