12
5. CONFIGURATION
- Settings may only be changed by a qualified electrical engineer.
- Read the instructions thoroughly before implementing changes.
- During setting of the charger, the DC fuse in the battery connections must be
removed.
5.1 Standard settings: ready for use
On delivery, the Quattro is set to standard factory values. In general, these settings are selected for single-unit operation.
Settings, therefore, do not require changing in the event of stand-alone use.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard Quattro factory settings
Inverter frequency
50 Hz
Input frequency range
45 - 65 Hz
Input voltage range
180 - 265 VAC
Inverter voltage
230 VAC
Stand-alone / parallel / 3-phase
stand-alone
AES (Automatic Economy Switch)
off
Ground relay
on
Charger on/ off
on
Charging characteristics
four-stage adaptive with BatterySafe mode
Charging current
75% of the maximum charging current
Battery type
Victron Gel Deep Discharge (also suitable for Victron AGM Deep
Discharge)
Automatic equalisation charging
off
Absorption voltage
14.4 / 28.8 / 57.6 V
Absorption time
up to 8 hours (depending on bulk time)
Float voltage
13.8 / 27.6 / 55.2 V
Storage voltage
13.2V (not adjustable)
Repeated absorption time
1 hour
Absorption repeat interval
7 days
Bulk protection
on
Generator (AC-in-1) / shore current (AC-in-2)
50A/16A (default setting, adjustable current limit for PowerControl and
PowerAssist functions)
UPS feature
on
Dynamic current limiter
off
WeakAC
off
BoostFactor
2
Programmable relay (3x)
alarm function
PowerAssist
on
Analog/digital input/output ports
programmable
Frequency shift
off
Built-in Battery Monitor
optional
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the
software configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1
(priority input) or AC-in-2. Once synchronised, the output frequency will be equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the Quattro. The Quattro synchronises within this range with the voltage present on AC-in-1 (priority
input) or on AC-in-2. After the back feed relay has closed, output voltage will be equal to input voltage.
Adjustability:
Lower limit: 180 - 230V
Upper limit: 230 - 270V
Inverter voltage
Output voltage of the Quattro in battery operation.
Adjustability: 210 – 245V
Содержание Quattro 24
Страница 2: ......
Страница 4: ......
Страница 58: ......
Страница 114: ......
Страница 161: ...19 EN NL FR DE ES SE Appendix Er ro r float Err or Ob temperatur ...
Страница 171: ...29 EN NL FR DE ES SE Appendix Er ro r float Err or Ob temperatur ...
Страница 190: ......
Страница 191: ...1 EN NL FR DE ES SE Appendix APPENDIX A Overview connections ...
Страница 196: ...6 APPENDIX C Parallel connection ...
Страница 197: ...7 EN NL FR DE ES SE Appendix APPENDIX D Three phase connection ...
Страница 200: ...10 APPENDIX G Dimensions ...
Страница 201: ......
Страница 202: ......
Страница 203: ......