background image

3.2.1. Battery connection

In order to fully utilize the full capacity of the inverter, it is important to use batteries with sufficient capacity and battery cables with
sufficient cross section.

There is no safety fuse inside the inverter. A safety fuse should be installed externally.

See below table for the recommended battery cable cross section, safety fuse rating and battery capacity for each inverter model.

Inverter

model

Cable cross section

0-5m

Cable cross section

5-10m

Fuse rating

Battery capacity

12/1600

1 x 70mm²

Not recommended

250A

300 - 800Ah

24/1600

1 x 35mm²

1 x 70mm²

125A

150 - 400Ah

48/1600

1 x 16mm²

1 x 25mm²

60A

75 - 200Ah

12/2000

1 x 70mm²

Not recommended

300A

350 - 1000Ah

24/2000

1 x 50mm²

1 x 95mm²

150A

200 - 500Ah

48/2000

1 x 25mm²

1 x 50mm²

80A

100 - 250Ah

12/3000

2 x 95mm² (*)

Not recommended

400A

400 - 1200Ah

24/3000

1 x 50mm²

2 x 50mm² (*)

250A

200 - 700Ah

48/3000

1 x 35mm²

2 x 35mm² (*)

125A

100 - 400Ah

24/5000

2 x 95mm² (*)

2 x 95mm² (*)

400A

300 - 1500Ah

48/5000

1 x 70mm²

2 x 70mm² (*)

200A

150 - 700Ah

(*) One cable must be sized to carry the rated fuse current without overheating. Do not locate battery cables in a closed conduit.
Please follow local installation rules.

Sufficient cable thickness and appropriate sized batteries are an important factor. Please consult your supplier or see the relevant
sections of our books: 

Energy Unlimited

 and 

Wiring Unlimited

, both downloadable from our website.

Battery connection procedure

Use an insulated box spanner in order to avoid shorting the battery.

The maximum torque is 11Nm.

Avoid shorting the battery cables.

Proceed as follows to connect the battery cables:

• Be aware that reverse polarity connection (+ to – and – to +) will cause damage to the inverter.

• Connect the battery cables to the + (red) and the - (black) battery terminals.

• Secure the battery connections tightly, while not exceeding the maximum 11Nm torque. A tight connection will reduce the

contact resistance as much as possible.

3.2.2. Solar connection

• Be aware that reverse polarity connection of the solar panel wires can cause damage to the inverter.

• Connect the solar panel cables to the positive (red) and the negative (black) PV terminals.

• Secure the PV connections tightly. A tight connection will reduce the contact resistance as much as possible.

3.2.3. Chassis to ground connection

Wire size for connecting the inverter chassis to ground:

The earth conductor from the earth lug on the chassis to ground should have at least half the cross-section of the conductors
used for the battery connection.

The earth lug on the chassis is a M6 bolt.

The AC output is not isolated from the DC input. The AC output Neutral is connected to chassis/ground. If the installation requires
a floating neutral, the neutral to ground link needs to be removed. See appendix 

Installation information floating ground 1600VA

and 2000VA models [20]

 or appendix 

Installation information floating ground 3000VA and 5000VA models [21]

 on how to do

this.

Phoenix Inverter Smart Manual

Page 5

Installation

Содержание Phoenix Inverter Smart

Страница 1: ...Phoenix Inverter Smart Manual Rev 00 05 2022 ENGLISH...

Страница 2: ...ect settings 7 4 3 1 Dynamic cut off 8 4 4 Programmable relay 9 4 5 Firmware update 9 4 6 Reset settings to default 10 5 Operation 11 5 1 Inverter 11 5 1 1 On Off Push button 11 5 1 2 On off Switch 5k...

Страница 3: ...t is likely that the grounding protection has been damaged the product must be turned off and secured against unintended operation please contact qualified service staff Ensure that the equipment is u...

Страница 4: ...d ECO mode sensitivity level Programmable relay To transfer the load to another AC source The automatic transfer switch For inverters we recommend our Filax2 automatic transfer switch The Filax2 featu...

Страница 5: ...additional VE Direct cable is needed for this 2 6 Remote on off control The inverter can be remotely turned on or off in the following ways Via the VictronConnect app With an optional external switch...

Страница 6: ...0 C humidity 95 non condensing Note that in extreme situations the inverter s case temperature can exceed 70 C Excessive high ambient temperature will result in a reduced service life reduced peak pow...

Страница 7: ...bsite Battery connection procedure Use an insulated box spanner in order to avoid shorting the battery The maximum torque is 11Nm Avoid shorting the battery cables Proceed as follows to connect the ba...

Страница 8: ...annot be accidentally turned back on by another user Inverter control panel If a Phoenix Inverter Control VE Direct panel is used it needs to be connected to the inverter remote connector as is indica...

Страница 9: ...load adjustable the inverter will go back to normal operation mode Once the load drops below a certain level the inverter will go back to ECO mode Below table indicates the default settings and settin...

Страница 10: ...elow graph shows the discharge ratio versus battery voltage curve for the different battery types You can see that the lithium curve LiFePO4 is nearly flat compared to the OPzV and OPzS curve The curv...

Страница 11: ...that it is time to do something charge the battery reduce the load and so forth in order to prevent a power outage Low battery Relay on during normal operation The relay will switch off once there is...

Страница 12: ...following way Navigate to the inverter settings by clicking on the cog symbol in the right top corner Click on the 3 dot symbol in the right top corner Select Reset to defaults from the menu and the s...

Страница 13: ...cut off the supply current completely The switch is located at the bottom right of the inverter next to the battery cable entries 5 1 3 ECO Mode The inverter can be switched to ECO mode via the Victr...

Страница 14: ...than the inverter rating and that if this situation continues the inverter will switch off due to an overload alarm Reduce the AC load The green inverter LED is blinking with a fast double pulse The r...

Страница 15: ...attery voltage alarm The inverter has shut down due to high battery voltage Reduce the DC input voltage check if the battery voltage is correct and if the battery bank is wired correctly Also check if...

Страница 16: ...ee the Dynamic cut off 8 chapter High battery voltage The inverter will shut down when the DC input voltage is too high The LEDs will signal shutdown due to high battery The inverter will first wait 3...

Страница 17: ...ring via a GX device GlobalLink and the VRM portal The inverter can be connected to a GX device like a Cerbo GX or a Color Control GX When connected the GX device will display the inverter on the syst...

Страница 18: ...load power in ECO mode 0 6 1 3 2 1W 0 6 1 3 2 1W 1 5 1 9 2 8W 2 2 3 2W GENERAL Programmable relay DC rating 4A 35V or 1A 60V AC rating 3A 230V Stop start power ECO mode Adjustable via VictronConnect a...

Страница 19: ...9 x 125mm 485 x 219 x 125mm 533 x 285 x 150mm 12V 485 x 285 x 150mm 24 28V 595 x 295 x 160mm 24V 555 x 295 x 160mm 48V STANDARDS Safety EN IEC 60335 1 Emission Immunity EN 55014 1 EN 55014 2 EN IEC 61...

Страница 20: ...7 Appendix 7 1 Connection overview Connections 1600VA model Connections 2000VA model Phoenix Inverter Smart Manual Page 18 Appendix...

Страница 21: ...Connections 3000VA model Phoenix Inverter Smart Manual Page 19 Appendix...

Страница 22: ...ation information floating ground 1600VA and 2000VA models Ground wire G connects the output neutral to ground It must be re positioned to a dummy terminal if a floating output is required When a floa...

Страница 23: ...eutral to ground It must be re positioned to a dummy terminal if a floating output is required When a floating output is obtained the current reading at no load can show an offset of around 100 150mA...

Страница 24: ...0000 Phoenix Inverter 24 1600 230V Smart PIN482160000 Phoenix Inverter 48 1600 230V Smart PIN122200000 Phoenix Inverter 12 2000 230V Smart PIN242200000 Phoenix Inverter 24 2000 230V Smart PIN482200000...

Страница 25: ...0 175 6 5 4 x 46 4 55 87 5 87 5 98 6 2 3 x 32 5 Rev00 Dimensions in mm Dimension Drawing Phoenix Inverter 3000VA Smart PIN122300000 Phoenix Inverter 12 3000 230V Smart D E F C 1 2 3 4 B A 3 2 1 5 C D...

Страница 26: ...87 5 87 5 98 6 2 3 x Rev00 Dimension Drawing Phoenix Inverter 3000VA Smart PIN242300000 Phoenix Inverter 24 3000 230V Smart PIN482300000 Phoenix Inverter 48 3000 230V Smart Dimensions in mm D E F C 1...

Страница 27: ...9 6 5 4 x 32 5 55 87 5 87 5 98 6 2 3 x Rev00 Dimension Drawing Phoenix Inverter 5000VA Smart PIN242500000 Phoenix Inverter 24 5000 230V Smart PIN482500000 Phoenix Inverter 48 5000 230V Smart Dimension...

Отзывы: