background image

Battery voltage

Low battery shutdown

Low battery restart & alarm

Charge detect

24V

Default: 18.6V

Range: 0-100V

Default: 21.8V

Range: 0-100V

Default: 28.0V

Range: 0-100V

48V

Default: 37.2V

Range: 0-100V

Default: 36.6V

Range: 0-100V

Default: 56.0V

Range: 0-100V

4.3.1. Dynamic cut off

The "Dynamic cut off" feature makes the low battery shutdown protection a function of the battery current drawn from the battery
in relation to the battery voltage.

When a high current is being drawn from the battery, a lower cut off voltage threshold is being used, for example 10V. And
similarly, when the battery is only being discharged slowly, a high cut off voltage is used, for example 11.5V.

In this way, a voltage drop, caused by the internal resistance in the battery, is compensated so that the battery voltage becomes a
much more reliable parameter to decide when to stop discharging the battery.

The "Dynamic cut off" feature is most useful for batteries with a high internal resistance, like OPzV and OPzS batteries. It is
a bit less relevant for GEL and AGM batteries and perhaps even irrelevant for lithium batteries. The below graph shows the
discharge ratio versus battery voltage curve for the different battery types. You can see that the lithium curve (LiFePO4) is nearly
flat compared to the OPzV and OPzS curve.

The curve can be adjusted in the VictronConnect app.

Discharge ratio versus battery voltage graph for different battery types

• Do not use the "Dynamic cut off" feature in an installation that also has other loads connected to the same

battery. In these systems the battery voltage might drop because of other loads connected to the battery.
The dynamic cut off algorithm in the inverter can not take those other loads into consideration and will shut
down the Inverter too early with an under voltage alarm.

VictronConnect settings

• The "Dynamic cut off" feature is disabled by default.

• Enable the "Dynamic cut off" feature to use and configure it.

• Select the battery type. Choose between: OPzV/OPzS, GEL/AGM, LiFePO4 or Custom.

• Enter the battery capacity.

• Enter the voltage for the various discharge currents. These values have already been set to the generic voltages that belong to

the specific battery type that was selected earlier. Change these settings only in case they need adjustment and you know what
you are doing, or in case a custom battery is being used.

Phoenix Inverter Smart Manual

Page 8

Configuration

Содержание Phoenix Inverter Smart

Страница 1: ...Phoenix Inverter Smart Manual Rev 00 05 2022 ENGLISH...

Страница 2: ...ect settings 7 4 3 1 Dynamic cut off 8 4 4 Programmable relay 9 4 5 Firmware update 9 4 6 Reset settings to default 10 5 Operation 11 5 1 Inverter 11 5 1 1 On Off Push button 11 5 1 2 On off Switch 5k...

Страница 3: ...t is likely that the grounding protection has been damaged the product must be turned off and secured against unintended operation please contact qualified service staff Ensure that the equipment is u...

Страница 4: ...d ECO mode sensitivity level Programmable relay To transfer the load to another AC source The automatic transfer switch For inverters we recommend our Filax2 automatic transfer switch The Filax2 featu...

Страница 5: ...additional VE Direct cable is needed for this 2 6 Remote on off control The inverter can be remotely turned on or off in the following ways Via the VictronConnect app With an optional external switch...

Страница 6: ...0 C humidity 95 non condensing Note that in extreme situations the inverter s case temperature can exceed 70 C Excessive high ambient temperature will result in a reduced service life reduced peak pow...

Страница 7: ...bsite Battery connection procedure Use an insulated box spanner in order to avoid shorting the battery The maximum torque is 11Nm Avoid shorting the battery cables Proceed as follows to connect the ba...

Страница 8: ...annot be accidentally turned back on by another user Inverter control panel If a Phoenix Inverter Control VE Direct panel is used it needs to be connected to the inverter remote connector as is indica...

Страница 9: ...load adjustable the inverter will go back to normal operation mode Once the load drops below a certain level the inverter will go back to ECO mode Below table indicates the default settings and settin...

Страница 10: ...elow graph shows the discharge ratio versus battery voltage curve for the different battery types You can see that the lithium curve LiFePO4 is nearly flat compared to the OPzV and OPzS curve The curv...

Страница 11: ...that it is time to do something charge the battery reduce the load and so forth in order to prevent a power outage Low battery Relay on during normal operation The relay will switch off once there is...

Страница 12: ...following way Navigate to the inverter settings by clicking on the cog symbol in the right top corner Click on the 3 dot symbol in the right top corner Select Reset to defaults from the menu and the s...

Страница 13: ...cut off the supply current completely The switch is located at the bottom right of the inverter next to the battery cable entries 5 1 3 ECO Mode The inverter can be switched to ECO mode via the Victr...

Страница 14: ...than the inverter rating and that if this situation continues the inverter will switch off due to an overload alarm Reduce the AC load The green inverter LED is blinking with a fast double pulse The r...

Страница 15: ...attery voltage alarm The inverter has shut down due to high battery voltage Reduce the DC input voltage check if the battery voltage is correct and if the battery bank is wired correctly Also check if...

Страница 16: ...ee the Dynamic cut off 8 chapter High battery voltage The inverter will shut down when the DC input voltage is too high The LEDs will signal shutdown due to high battery The inverter will first wait 3...

Страница 17: ...ring via a GX device GlobalLink and the VRM portal The inverter can be connected to a GX device like a Cerbo GX or a Color Control GX When connected the GX device will display the inverter on the syst...

Страница 18: ...load power in ECO mode 0 6 1 3 2 1W 0 6 1 3 2 1W 1 5 1 9 2 8W 2 2 3 2W GENERAL Programmable relay DC rating 4A 35V or 1A 60V AC rating 3A 230V Stop start power ECO mode Adjustable via VictronConnect a...

Страница 19: ...9 x 125mm 485 x 219 x 125mm 533 x 285 x 150mm 12V 485 x 285 x 150mm 24 28V 595 x 295 x 160mm 24V 555 x 295 x 160mm 48V STANDARDS Safety EN IEC 60335 1 Emission Immunity EN 55014 1 EN 55014 2 EN IEC 61...

Страница 20: ...7 Appendix 7 1 Connection overview Connections 1600VA model Connections 2000VA model Phoenix Inverter Smart Manual Page 18 Appendix...

Страница 21: ...Connections 3000VA model Phoenix Inverter Smart Manual Page 19 Appendix...

Страница 22: ...ation information floating ground 1600VA and 2000VA models Ground wire G connects the output neutral to ground It must be re positioned to a dummy terminal if a floating output is required When a floa...

Страница 23: ...eutral to ground It must be re positioned to a dummy terminal if a floating output is required When a floating output is obtained the current reading at no load can show an offset of around 100 150mA...

Страница 24: ...0000 Phoenix Inverter 24 1600 230V Smart PIN482160000 Phoenix Inverter 48 1600 230V Smart PIN122200000 Phoenix Inverter 12 2000 230V Smart PIN242200000 Phoenix Inverter 24 2000 230V Smart PIN482200000...

Страница 25: ...0 175 6 5 4 x 46 4 55 87 5 87 5 98 6 2 3 x 32 5 Rev00 Dimensions in mm Dimension Drawing Phoenix Inverter 3000VA Smart PIN122300000 Phoenix Inverter 12 3000 230V Smart D E F C 1 2 3 4 B A 3 2 1 5 C D...

Страница 26: ...87 5 87 5 98 6 2 3 x Rev00 Dimension Drawing Phoenix Inverter 3000VA Smart PIN242300000 Phoenix Inverter 24 3000 230V Smart PIN482300000 Phoenix Inverter 48 3000 230V Smart Dimensions in mm D E F C 1...

Страница 27: ...9 6 5 4 x 32 5 55 87 5 87 5 98 6 2 3 x Rev00 Dimension Drawing Phoenix Inverter 5000VA Smart PIN242500000 Phoenix Inverter 24 5000 230V Smart PIN482500000 Phoenix Inverter 48 5000 230V Smart Dimension...

Отзывы: