4. Operation 

 

4.1 LED definitions 

Green LED 

Status

 

Trouble shooting 

●●●●●●●●

 

Solid on

 

Inverter on 

Red LED Off 

status OK 
 

Red LED On or blinking: 

The Inverter is still on and but will shut down when the 
condition gets worse. See red LED table for warning reason 

●●------ 

Slow single pulse

 

ECO mode 

If the inverter keeps switching on and off, while there is a load 
connected, the load may be too small compared to the actual 
ECO mode settings. Increase the load or change ECO mode 
settings. 

●-●----- 

Fast double pulse

 

Off and waiting  Inverter did shut down because of a protection. The inverter 

will restart automatically as soon as all alarm conditions are 
cleared. See red LED state for the shutdown reason.  

-------- 

Off

 

Inverter off 

Red LED Off 

Check the On/Off/ECO switch: it should be in On position or in 
ECO position. 
Check Remote on/off connector. 
Check DC cable connections and fuses. 
Inverter fuse blown: the inverter has to be returned for service. 
 

Red LED On or blinking

 

The inverter did shut down because of a protection. It will no 
longer automatically restart. The red LED indicates the reason 
for shutdown. Remove the cause and then restart the inverter 
by switching it Off, and then back On. 

 

Red LED 

Definition

 

Trouble shooting 

●●●●●●●●

 

Solid on

 

Overload 

Reduce load 

●●●●----

 

Slow blink

 

Low batt. 

Recharge or replace battery 
Check DC cable connections  
Check cable cross section as it may be insufficient. 
See section 4.3 Protections and automatic restarts for manual 
and automatic restart behavior. 

●-●-●-●-

 

Fast blink

 

High batt. 

Reduce DC input voltage, check for faulty charger 

●-●-----

 

Double pulse

 

High temp. 

Reduce load and/or move inverter to better ventilated area 

●---●---

 

Fast single pulse

 

High DC ripple  Check DC cable connections and cable cross section.  

 

4.2 ECO Mode 

Set the front switch to ECO mode to reduce the power consumption in no-load 
operation. The inverter will automatically switch off as soon as it detects that there is 
no load connected. It then switches on, briefly, every 2,5 seconds to detect a load. If 
the output power exceeds the set level, the inverter will continue to operate.  
 
The default ECO mode wake-up minimum power is 25 Watt 
The default ECO mode search interval is 2.5 seconds 
 
Note that the required ECO mode settings are heavily dependent on the type of load: 
inductive, capacitive, non-linear. Adjustment may be needed. 
 

Содержание Phoenix 12/250

Страница 1: ...Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 24 250 24 375 48 250 48 375...

Страница 2: ......

Страница 3: ...assis must be grounded A grounding point is located on the outside of the product Whenever it is likely that the grounding protection has been damaged the product must be turned off and secured agains...

Страница 4: ...reliability over many years The inverters are short circuit proof and protected against overheating whether due to overload or high ambient temperature High start up power Needed to start loads such a...

Страница 5: ...C circuit breaker must be inserted close to the battery Reverse polarity connection of the battery wires will blow the internal fuse and can damage the inverter The internal fuse it not replacable 3 2...

Страница 6: ...LED indicates the reason for shutdown Remove the cause and then restart the inverter by switching it Off and then back On Red LED Definition Trouble shooting Solid on Overload Reduce load Slow blink L...

Страница 7: ...it Off and then On or recharge the battery as soon as the battery has risen and then stayed above the Charge detect level for 30 seconds it will switch on See the Technical Data table for default low...

Страница 8: ...2 a f Operating temperature range 40 to 60 C fan assisted cooling derate 3 per C above 40 C Humidity non condensing max 95 ENCLOSURE Material Colour Steel chassis and plastic cover blue Ral 5012 Batt...

Страница 9: ...EN NL FR DE ES Appendix the Digital Multi Control Fig 1 Front and rear view FigFi...

Страница 10: ...00 Date 20 January 2016 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 Customer support desk 31 0 36 535 97 03 Fax 31 0 36 535...

Отзывы: