8
4.2 Connection of Battery cables
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table.
12/1600 24/1600 48/1600 12/2000 24/2000 48/2000
Recommended
cross section (mm
2
)
length up to 6 m
50
25
25
70
35
25
12/1600
24/1600
48/1600
12/2000
24/2000
48/2000
Recommended
battery capacity
(Ah)
300 - 800 150 - 400 75 - 200 350 - 1000 200 - 500 100 - 250
Remark: Internal resistance is the important factor when working with low capacity batteries.
Please consult your supplier or the relevant sections of our book “electricity on board”,
downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Connect the battery cables: the + (red) and the - (black), to the battery see appendix A.
Reverse polarity connection (+ to – and – to +) will cause damage to the product.
Secure the nuts tightly in order to reduce the contact resistance as much as possible.
4.3 DC safety fuse
There is no safety fuse inside the inverter; this should be installed externally. The
recommended safety fuses can be found in the table below
12/1600
24/1600
48/1600
12/2000
24/2000
48/2000
Recommended
DC fuse
250A
125A
60A
300A
150A
80A