4.4.6 Parallel Connection
The MultiPlus can be connected in parallel with several identical devices. To this
end, a connection is established between the devices by means of standard RJ45
UTP cables. The
system
(one or more MultiPlus units plus optional control panel)
will require subsequent configuration (see Section 5).
In the event of connecting MultiPlus units in parallel, the following requirements
must be met:
- A maximum of six units connected in parallel.
- Only identical devices may be connected in parallel.
- The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the connection
between the batteries and the DC distribution point must at least equal the sum of the required
cross-sections of the connections between the distribution point and the MultiPlus units.
- Place the MultiPlus units close to each other, but allow at least 10 cm / 4 inch for ventilation
purposes under, above and beside the units.
- UTP cables must be connected directly from one unit to the other (and to the remote panel).
Connection/splitter boxes are not permitted.
- A battery-temperature sensor need only be connected to one unit in the system. If the
temperature of several batteries is to be measured, you can also connect the sensors of other
MultiPlus units in the system (with a maximum of one sensor per MultiPlus). Temperature
compensation during battery charging responds to the sensor indicating the highest temperature.
- Voltage sensing must be connected to the master (see Section 5.5.1.4).
- If more than three units are connected in parallel in one system, a dongle is required (see
Section 5).
- Only one remote control (panel or switch) can be connected to the
system
.
4.4.7 Three-phase operation
The MultiPlus can also be used in 3-phase configuration. To this end, a connection
between the devices is made by means of standard RJ45 UTP cables (the same as
for parallel operation). The
system
(MultiPlus units plus an optional control panel) will
require subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.6.
4.4.8 Two phase (split phase) configuration (see appendix C)
MultiPlus units can also be used in split phase configuration. To this end, a
connection between the devices is made by means of standard RJ45 UTP cables (the
same as for parallel operation). The
system
(MultiPlus units plus an optional control
panel) will require subsequent configuration (see Section 5).
Pre-requisites: see Section 4.4.6.
Содержание MultiPlus 12/3000/120 - 50
Страница 1: ...Manual EN Appendix MultiPlus 12 3000 120 50 120V 24 3000 70 50 120V ...
Страница 2: ......
Страница 4: ......
Страница 50: ......
Страница 51: ...EN Appendix www victronenergy com APPENDIX A Overview connections B H I J F E G A C K L ...
Страница 53: ...EN Appendix www victronenergy com APPENDIX B Block diagram See table in section 4 2 ...
Страница 58: ...APPENDIX G Dimensions ...
Страница 59: ...EN Appendix www victronenergy com ...
Страница 60: ......
Страница 61: ...www victronenergy com ...