For both, the connector can be pulled free for easy wiring, and then re-insterted.

2.4.2. 

#

 Digital inputs

The Maxi GX has four digital inputs. The operate at 3v3 levels, and can withstand up to 5V input. Each input has an
internal 10k pull-up resistor to 3v3. We recommend wiring it to a potential free relay or otherwise an open
collector/optocoupler output.

The terminal block has four pairs of two terminals:

The two on the left are digital input one (open or short them), the next two are digital input 2, and-so-forth. Where
upper row is signal and lower row is GND for all four inputs.

D1

D2

D3

D4

GND

GND

GND

GND

2.4.3. 

#

 Relays

Relay 1 can be used for auto-starting a generator, an alarm relay, and as a free to use remotely operable relay via the
graphical interface. Relay 2 can be operated via a selection from graphical interface, but not used with the built in
autostart generator or alarm relay features.

Relay 1

NO

COM

NC

Содержание Maxi GX

Страница 1: ...s with a VE Direct port it has a fast CPU and 25 VE Direct ports Inside the steel enclosure is a power supply a GX controller board and various other components This picture shows the complete insides 2 Installation 2 1 Mounting The Maxi GX is a steel IP67 enclosure made by Rittal part number AE 1038 500 Mount the unit using the four brackets ...

Страница 2: ...functional and connecting it will lead to a hardware failure Connect ethernet to the socket labeled ETH on the controller board The dual RJ45 VE Can socket on the bottom of the controller board can be used to connect to either a battery equipped with a Can BUS BMS Or to one or more Victron products equipped with a VE Can port Up to 25 VE Direct devices can be connected to the available VE Direct p...

Страница 3: ...ut The terminal block has four pairs of two terminals The two on the left are digital input one open or short them the next two are digital input 2 and so forth Where upper row is signal and lower row is GND for all four inputs D1 D2 D3 D4 GND GND GND GND 2 4 3 Relays Relay 1 can be used for auto starting a generator an alarm relay and as a free to use remotely operable relay via the graphical int...

Страница 4: ... for DHCP And then on a computer with internet go to our VRM Portal and follow the instructions in VRM Portal chapter of the CCGX Manual Alternatively on the local network the device can be easily found with VictronConnect This video shows how that is done Use the push button to cycle to the LAN ip address page 4 Configuration and operation Refer to the CCGX Manual 5 Troubleshooting Below picture s...

Страница 5: ...gx maxi gx 5 5 red power LED on the controller board on the right red power LED on the USB hub LEDs per USB connection on the USB hub For other possible issues refer to the CCGX Manual ...

Отзывы: