Lynx Smart BMS alarms on the VictronConnect App and a GX device
The following tables list all warning, alarm and error codes:
VictronCo
nnect
warning
code
GX device
warning
code
Message
Instructions / remarks
W-B01
Low cell
voltage
Low cell voltage
Charge the battery or reduce the load to prevent an
imminent system shutdown.
W-B02
#105 or
#106
High current
Reduce the current to prevent an imminent system
shutdown. Do this by reducing the load or by turning
loads off.
W-B03
#101
High BMS temperature
Check the ambient temperature and check if the
BMS fans are running. If the fans are running,
reduce the ambient temperature. If the fans are not
running, contact your Victron dealer.
W-B04
#112
Warning bad contactor
Reduce the current to prevent an imminent system
shutdown. Do this by reducing the load or by turning
loads off. Contact your Victron dealer.
W-B06
-
Load will disconnect
The loads will be turned off in 30 seconds if fault is
not resolved. For example low battery voltage. This
warning is always in combined the reason why the
load will disconnect.
The loads are turned off via the ATD contact and/or
via the GX device.
W-D01
#221
Communication with distributor A
lost
Check the cable between BMS and Distributor.
W-D02
#222
Communication with distributor B
lost
Check the cable between BMS and Distributor.
W-D03
#223
Communication with distributor C
lost
Check the cable between BMS and Distributor.