13. Error Codes
Different origins of errors
On your GX device, some error codes shown will be from the GX device itself, in that case see below list. As the system control
panel, it also shows error codes from the connected devices.
• Multi and Quattro inverter/chargers:
MPPT Solar Charger Error Codes
GX Error #42 - Storage corrupt
This error means that the flash memory inside the GX Device is corrupt.
The device must be sent in for repair/replacement. It is not possible to correct this issue in the field or with a firmware update.
The affected flash memory is the partition that holds all user settings and factory data, such as serial numbers and wifi codes.
GX Error #47 - Data partition issue
The internal storage in the GX Device is most likely broken: causing it to loose its configuration.
Contact your dealer or installer; see
GX Error #48 - DVCC with incompatible firmware
This error is raised when the DVCC feature is enabled whilst not all devices in the system are updated to recent enough firmware.
More information about DVCC and minimal required firmware versions in chapter 4 of this manual.
Note for systems with BYD, MG Energy Systems, and Victron Lynx Ion BMS batteries:
Since Venus OS v2.40, released in December 2019, the DVCC feature is automatically switched on when the system detects a
supported battery/BMS type connected. In systems that require DVCC to be enabled by the battery manufacturers, it is now no
longer possible to switch DVCC off.
This creates an issue for systems installed and commissioned a long time ago, before DVCC was available, and they may not
have the other necessary components or firmware to work correctly with it enabled.
The solution is to:
1. Disable automatic updates; Settings → Firmware → Online updates.
2. Roll back to v2.33; See Settings, Firmware and then Stored backup firmware.
3. Make sure that DVCC is disabled again.
Please do consult your installer, to check if the battery system is managed with two wire control (an earlier alternative control
method to DVCC) or not:
If there is no charge- and discharge- wiring between BMS, inverter/chargers and charge controllers, then DVCC is required for
above mentioned battery brands, and this also has certain minimum firmware requirements for connected Inverter/chargers and
Solar charge controllers.
What's new since Venus OS v2.40 is (a) that it automatically enables DVCC when it sees the above mentioned battery types, and
(b) that when DVCC is enabled, it checks the connected devices for the minimum firmware, and raises Error #48 in case the
firmware of one or more connected devices is too old.
GX Error #49 - Grid meter not found
This warning is raised in an ESS system when Grid metering is configured to use an External meter, but no meter is present. This
alerts installers and end-users that the system is not correctly configured, or cannot operate correctly because it cannot
communicate with the grid meter.