Item
Default
Description
GPS
-
Read full feature description [7]
GPS information
Status, Latitude, Longitude, Speed, Course, Altitude, Number of
satellites
Format
Select the format in which to show the Latitude and Longitude.
Speed unit
km/h
Choose between km/h, meters per second, miles per hour, or
knots.
Device
Connected, Connection, Product, Product ID, Firmware version,
Device instance
Generator start/stop
Configure generator autostart settings and conditions.
State
Displays if the generator is running or not
Error
Displays if there is error (eg generator is supposed to be running
but no AC input is detected)
Total run time
Total time the generator has been running since reset.
Time to next test run
If a periodic run is programmed, this counter will display in days,
and hours how long before that will occur.
Auto start functionality
Enable or Disable the Autostart functions, this can be further
configured in the Generator -> Settings -> Conditions menu
Manual start
Start generator, Run for hh:mm
Daily run time
Submenu shows the history of time generator has been running
(minutes) each day for the previous 30 days.
Generator start/stop -> Settings
Generator start/stop -> Settings -> Conditions
On loss of communication
Stop generator
Stop, Start, Keep generator running
Do not run generator when
AC1 is in use
No
This option is ideal for back-up systems where a Quattro has
mains/grid electricity connected to its AC-in 1 terminal, and a
Genset connected to its AC-in 2 terminal. With this option
enabled, the Genset will only start after a mains failure.
Battery SOC
No
Use Battery SOC value to start/stop - No / Yes
Start when SOC is lower than - %
Start value during quiet hours - % (to override programmed quiet
hours when absolutely necessary)
Stop when Battery SOC is higher than - %
Stop value during quiet hours - % (allows for less runtime during
quiet hours, once system is recovered)
Battery current
Battery voltage
AC output
No
Use value to start/stop - No / Yess
Start when value is higher than - Amps / Voltage / Watts
Start value during quiet hours - Amps / Voltage / Watts (to
override programmed quiet hours when absolutely necessary)
Start after condition is reached for - seconds (to allow for
momentary spikes to pass without triggering start)
Stop when value is lower than - Amps / Voltage / Watts
Stop value during quiet hours - Amps / Voltage / Watts (allows for
less runtime during quiet hours, once system is recovered)
Stop after the condition is reached for - seconds (to allow for
momentary dips without stopping the running generator)
Inverter high temperature
Inverter overload
No
Start on value warning - No / Yes
Start when warning is active for - seconds (to allow for
momentary spikes to pass without triggering start)
When warning is cleared stop after - seconds (to allow for
momentary dips without stopping the running generator)
Generator start/stop -> Settings -> Conditions -> Periodic run
Color Control GX Manual
Page 25