background image

 

 

COMPLETE MAINTENANCE – FIVE YEAR TEARDOWN / HYDROTESTING 

 

[NFPA-10]  Every  five  years,  stored  pressure  water  mist  extinguishers  require  a  five-year 

hydrostatic  test  shall  be  emptied  and  subjected  to  the  applicable  maintenance  procedures.   

When  the  applicable  maintenance  procedures  are  performed  during  periodic  recharging  or 

hydrostatic testing, the five-year requirement shall begin from that date. 

 

NOTE: Some states have legislation which requires "Complete Maintenance" on an annual basis. 

Please contact your local Victory Distributor to see if these requirements apply to you. 

 

1.

 

Discharge  extinguishers  to  release  pressure  and  water  mist.  Make  sure  that  the  extinguisher  is 

completely  empty  and  depressurized.  To  depressurize  –  hold  the  extinguisher  in  an  inverted 

position and slowly squeeze the discharge handle and lever. See trouble shooting section for more 

details 

2.    Clean  extinguisher  to  remove  dirt,  grease,  or  foreign  material.    Check  to  make  sure  that  the 

instruction  nameplate  is  securely  fastened  and  legible.    Inspect  the  cylinder  for  corrosion, 

abrasion, dents, or weld damage or use of substitute parts.    If any of these conditions are found 

and you doubt the integrity of the cylinder, hydrostatically test to factory test pressure marked on 

the nameplate (label), using the proof pressure method, in accordance with CGA C-1 and NFPA 

10. Any distortion or leakage of the cylinder shall be cause for rejection. 

NOTE:  When  cleaning,  avoid  use  of  solvents  around  the  pressure  gauge.  They  could 

seriously damage the plastic gauge face.

 

3. 

Inspect  the  extinguisher  for  damaged,  missing  or  substitute  parts. 

NOTE:  Only  factory 

replacement parts are approved for use on victory fire extinguishers. 

4.    Check the date of manufacture on the extinguisher label (nameplate or cylinder). Cylinder must be 

hydrostatically  (proof  pressure)  tested  every  five  years  to  the  test  pressure  indicated  on  the 

nameplate. Any distortion or leakage of the cylinder shall be cause for rejection. Never place an 

extinguisher  back  into  service  if  hydro  test  is  overdue.  Always  complete  hydro  test  and  if 

acceptable return to service. 

5.    Visually inspect the pressure gauge – if bent, damaged or improper type or pressure – replace with 

the proper Victory pressure gauge (see Parts List).   

6.    Check  ring  (safety)  pin  for  freedom  of  movement.    Replace  if  bent  or  if  removal  appears 

difficult.   

7.    Inspect  discharge  lever  for  any  dirt  or  corrosion  which  might  impair  freedom  of  movement.   

Inspect  carrying  handle  for  proper  installation.    If  lever,  handle,  or  rivets  are  damaged,  replace 

with proper Victory parts.   

8.    Remove hose assembly and visually inspect threads on hose coupling, hose for damage, and   

replace,  as  necessary.    Blow  air  through  nozzle  and  hose  to  ensure  passage  is  clear  of  foreign 

material or obstructions. 

9.    Inspect  the  valve  assembly  for  corrosion  or  damage  to  hose  thread  connection.    Replace  valve 

assembly or component parts, as necessary. 

 

10.    Remove and disassemble valve assembly by removing dip tube, spring, and valve stem assembly. 

Install a new valve stem and collar O-ring after lightly lubricating with Visilox V- 711.    (Do not 

lubricate valve stem seal.)   

11.    Complete steps 3 through 15 of Recharge Procedure.   

 

Содержание WM2.5GAL

Страница 1: ...at they are ready to operate properly and safely Victory strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your local authorized Victory Distrib...

Страница 2: ...D FAILURE TO HEED THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY VICTORY ASSUMES NO LIABILITY FOR SERVICE MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS MANUAL REFERENCES IN THIS...

Страница 3: ...to 49 C please see the nameplate on your extinguisher The extinguisher should be adequately protected if temperatures outside of this range are anticipated Keep the extinguisher clean and free from d...

Страница 4: ...the extinguisher in a vertical position aim the nozzle at the base of the fire 5 Approach fire from upwind minimum of 10 feet of the front edge of the fire 6 Starting back from this distance squeeze t...

Страница 5: ...sher connected to a regulator of a high pressure source for an extended period A defective regulator could cause the cylinder to rupture due to excessive pressure CAUTION Discharge time and effective...

Страница 6: ...ondition to prevent its operation and any necessary repair or replacement It will normally reveal if hydrostatic testing or internal maintenance is required Maintenance servicing recharging shall be p...

Страница 7: ...te the class C capability Do not mix deionized water with non deionized in extinguisher content 6 Visually inspect the pressure gauge a If bent damaged or improper gauge depressurize and replace b If...

Страница 8: ...could seriously damage the plastic gauge face 3 Inspect the extinguisher for damaged missing or substitute parts NOTE Only factory replacement parts are approved for use on victory fire extinguishers...

Страница 9: ...disassembled valve with a soft bristle brush or soft cloth Blow the valve out with air or nitrogen Inspect the collar O ring valve stem spring and dip tube assembly and replace parts if worn or damage...

Страница 10: ...ing facing the front of the extinguisher gauge side 12 Install new tamper seal wrapping through loop and around levers to secure ring pin Do not over stress tamper seal 13 Weigh assembled extinguisher...

Страница 11: ...ent De pressurize and replace Install the correct Victory pressure gauge using Teflon tape on the gauge threads 9 Gauge does not indicate compatible with brass De pressurize and replace Install the co...

Страница 12: ...will not affect the remainder Victory is not responsible for the installation or the maintenance of the products Defective products for which a valid claim has been made shall be returned to Victory s...

Страница 13: ...sociation 2022 Edition 1 Batterymarch Pk P O Box 9101 Quincy MA 02169 7471 www nfpa org CGA C 1 Methods for Hydrostatic Compressed Gas Assoc Inc Testing of Compressed Gas 4221 Walney Road 5th floor Cy...

Страница 14: ...14 APPENDIX A...

Страница 15: ...ch Pressure Gauge to valve Recommended torque 5 12Nm 44 106 in lbs with sealant glue Scales Filling cylinders with deionized water Recommended accuracy 2 5 or better Pressurizing recharging adaptors S...

Отзывы:

Похожие инструкции для WM2.5GAL