PERIODIC INSPECTION PROCEDURES 

(Monthly or more often if circumstances dictate) 

   

[NFPA-10]  Periodic  inspection  of  fire  extinguishers  shall  include  a  check  of  at  least  the  following 

items:   

1.    Location in designated place.   

2.    Visibility of extinguisher or means of indicating the extinguisher location   

3.    Pressure gauge reading or indicator in the operable range or position.   

4.    Fullness determined by weighing or hefting. 

5.    Operating instructions on nameplate and facing outward.   

6.    Safety seals and tamper indicators not broken or missing.   

7.    Examination for obvious physical damage, corrosion, leakage, or clogged nozzle.   

8. 

Date and initial the inspection tag or record in accordance with NFPA-10 or local requirements     

 

MAINTENANCE 

 

[NFPA-10] At least once a year or more frequently if circumstances require, maintenance should 

be  performed.    Maintenance  is  a  "thorough  check"  of  the  extinguisher.    It  is  intended  to  give 

maximum  assurance  that  a  fire  extinguisher  will  operate  effectively  and  safely.    It  includes  a 

thorough  examination  for  physical  damage  or  condition  to  prevent  its  operation  and  any 

necessary  repair  or  replacement.    It  will  normally  reveal  if  hydrostatic  testing  or  internal 

maintenance is required.   

   

Maintenance,  servicing  &  recharging  shall  be  performed  by  trained  and  certified  persons  having 

available the appropriate servicing manual, the proper types of tools, recharge materials, lubricants, and 

Victory replacement parts.       

   

Extinguishers taken out of service for maintenance or recharge shall be replaced by spare extinguishers 

of the same type and at least an equal rating.   

 

MAINTENANCE – SERVICE PROCEDURE 

 

FIRE  EXTINGUISHERS  SHALL  BE  SUBJECT  TO  MAINTENANCE  AT  INTERVALS  OF 

NOT  MORE  THAN  ONE  YEAR,  AT  TIME  OF  HYDROSTATIC  TEST  OR  WHEN 

SPECIFICALLY  INDICATED  BY  AN  INSPECTION  DISCREPANCY.  MAINTENANCE 

EXAMINATION  WILL  IDENTIFY  THE  NEED  FOR  REPLACEMENT,  REPAIR  AND  IF 

HYDROSTATIC TESTING IS REQUIRED 

WARNING 

Before servicing check the extinguisher is correctly pressurized.   

This procedure is best accomplished with the extinguisher in an upright position and on a level 

surface. 

   

1.    Ensure  extinguisher  is  installed  in  proper  location  and  that  it  is  readily  accessible.  (Water  mist 

extinguishers  are  approved  for  temperature  ranges  between  +40°  F  to  +120°  F  and  need  to  be 

protected from freezing. 

Содержание WM2.5GAL

Страница 1: ...at they are ready to operate properly and safely Victory strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your local authorized Victory Distrib...

Страница 2: ...D FAILURE TO HEED THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY VICTORY ASSUMES NO LIABILITY FOR SERVICE MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS MANUAL REFERENCES IN THIS...

Страница 3: ...to 49 C please see the nameplate on your extinguisher The extinguisher should be adequately protected if temperatures outside of this range are anticipated Keep the extinguisher clean and free from d...

Страница 4: ...the extinguisher in a vertical position aim the nozzle at the base of the fire 5 Approach fire from upwind minimum of 10 feet of the front edge of the fire 6 Starting back from this distance squeeze t...

Страница 5: ...sher connected to a regulator of a high pressure source for an extended period A defective regulator could cause the cylinder to rupture due to excessive pressure CAUTION Discharge time and effective...

Страница 6: ...ondition to prevent its operation and any necessary repair or replacement It will normally reveal if hydrostatic testing or internal maintenance is required Maintenance servicing recharging shall be p...

Страница 7: ...te the class C capability Do not mix deionized water with non deionized in extinguisher content 6 Visually inspect the pressure gauge a If bent damaged or improper gauge depressurize and replace b If...

Страница 8: ...could seriously damage the plastic gauge face 3 Inspect the extinguisher for damaged missing or substitute parts NOTE Only factory replacement parts are approved for use on victory fire extinguishers...

Страница 9: ...disassembled valve with a soft bristle brush or soft cloth Blow the valve out with air or nitrogen Inspect the collar O ring valve stem spring and dip tube assembly and replace parts if worn or damage...

Страница 10: ...ing facing the front of the extinguisher gauge side 12 Install new tamper seal wrapping through loop and around levers to secure ring pin Do not over stress tamper seal 13 Weigh assembled extinguisher...

Страница 11: ...ent De pressurize and replace Install the correct Victory pressure gauge using Teflon tape on the gauge threads 9 Gauge does not indicate compatible with brass De pressurize and replace Install the co...

Страница 12: ...will not affect the remainder Victory is not responsible for the installation or the maintenance of the products Defective products for which a valid claim has been made shall be returned to Victory s...

Страница 13: ...sociation 2022 Edition 1 Batterymarch Pk P O Box 9101 Quincy MA 02169 7471 www nfpa org CGA C 1 Methods for Hydrostatic Compressed Gas Assoc Inc Testing of Compressed Gas 4221 Walney Road 5th floor Cy...

Страница 14: ...14 APPENDIX A...

Страница 15: ...ch Pressure Gauge to valve Recommended torque 5 12Nm 44 106 in lbs with sealant glue Scales Filling cylinders with deionized water Recommended accuracy 2 5 or better Pressurizing recharging adaptors S...

Отзывы:

Похожие инструкции для WM2.5GAL