APPENDIX B 

Equipment Type 

Where Used   

Comments 

Adjustable Wrench or 

23mm open ended wrench 

Hose and Wand 

Assembly to valve 

Recommended torque   

5Nm (44 in lbs.) 

Adjustable Wrench or 

19mm open ended wrench 

Lance/Wand to Hose 

Assembly 

Recommended torque   
3-5Nm (26-44 in lbs.) 

Adjustable Wrench or 

15mm open ended wrench 

Nozzle to lance/wand 

Recommended torque   
3-5Nm (26-44 in lbs.) 

Adjustable Wrench or 7/8” 

open ended wrench 

Siphon Tube Assembly 

to valve 

Recommended torque   

8Nm (71 in lbs.) 

11mm (7/16”) open ended 

wrench 

Pressure Gauge to valve 

Recommended torque   

5-12Nm (44-106 in lbs.) with sealant/glue   

Scales   

Filling cylinders with 

deionized water 

Recommended accuracy   

+/- 2.5% or better 

Pressurizing / recharging 

adaptors   

See table below for application 

Regulated Gauge 

Pressurizing 

Use regulated gauge set when pressurizing the extinguisher. 

NOTE

: Do not set pressure on regulator more than 25 psi 

above working pressure shown on the gauge 

Hand / Wrench 

Valve collar to cylinder 

Recommended torque   

20-30Nm (15-22 ft lbs.) 

Lubricant 

Neck to valve seal and 

blow by O seal on stem 

Recommended lubricant Visilox V-711 

 

Change History 

Date 

Revision    Change Details 

04/20/2022  1 

First release   

04/21/2022  2 

Updated for UL files and Website 

 

Содержание WM2.5GAL

Страница 1: ...at they are ready to operate properly and safely Victory strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your local authorized Victory Distrib...

Страница 2: ...D FAILURE TO HEED THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY VICTORY ASSUMES NO LIABILITY FOR SERVICE MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS MANUAL REFERENCES IN THIS...

Страница 3: ...to 49 C please see the nameplate on your extinguisher The extinguisher should be adequately protected if temperatures outside of this range are anticipated Keep the extinguisher clean and free from d...

Страница 4: ...the extinguisher in a vertical position aim the nozzle at the base of the fire 5 Approach fire from upwind minimum of 10 feet of the front edge of the fire 6 Starting back from this distance squeeze t...

Страница 5: ...sher connected to a regulator of a high pressure source for an extended period A defective regulator could cause the cylinder to rupture due to excessive pressure CAUTION Discharge time and effective...

Страница 6: ...ondition to prevent its operation and any necessary repair or replacement It will normally reveal if hydrostatic testing or internal maintenance is required Maintenance servicing recharging shall be p...

Страница 7: ...te the class C capability Do not mix deionized water with non deionized in extinguisher content 6 Visually inspect the pressure gauge a If bent damaged or improper gauge depressurize and replace b If...

Страница 8: ...could seriously damage the plastic gauge face 3 Inspect the extinguisher for damaged missing or substitute parts NOTE Only factory replacement parts are approved for use on victory fire extinguishers...

Страница 9: ...disassembled valve with a soft bristle brush or soft cloth Blow the valve out with air or nitrogen Inspect the collar O ring valve stem spring and dip tube assembly and replace parts if worn or damage...

Страница 10: ...ing facing the front of the extinguisher gauge side 12 Install new tamper seal wrapping through loop and around levers to secure ring pin Do not over stress tamper seal 13 Weigh assembled extinguisher...

Страница 11: ...ent De pressurize and replace Install the correct Victory pressure gauge using Teflon tape on the gauge threads 9 Gauge does not indicate compatible with brass De pressurize and replace Install the co...

Страница 12: ...will not affect the remainder Victory is not responsible for the installation or the maintenance of the products Defective products for which a valid claim has been made shall be returned to Victory s...

Страница 13: ...sociation 2022 Edition 1 Batterymarch Pk P O Box 9101 Quincy MA 02169 7471 www nfpa org CGA C 1 Methods for Hydrostatic Compressed Gas Assoc Inc Testing of Compressed Gas 4221 Walney Road 5th floor Cy...

Страница 14: ...14 APPENDIX A...

Страница 15: ...ch Pressure Gauge to valve Recommended torque 5 12Nm 44 106 in lbs with sealant glue Scales Filling cylinders with deionized water Recommended accuracy 2 5 or better Pressurizing recharging adaptors S...

Отзывы:

Похожие инструкции для WM2.5GAL