background image

 

 

STORED PRESSURE, HAND PORTABLE   
WATER MIST FIRE EXTINGUISHERS   
MODELS:    WM6L/ WM2.5GAL 

 

Owner’s SERVICE MANUAL   

No. ZX-UL-SM005 Rev.2   

 

INSTALLATION, OPERATING & SERVICING INSTRUCTIONS 

 

All  fire  extinguishers  should  be  installed,  inspected,  and  maintained  in  accordance  with  the  National 

Fire  Protection  Association  standard  titled  "Portable  Fire  Extinguishers",  NFPA-10  and  the 

requirements of local authorities having jurisdiction. 

 

When  installation,  inspection  or  maintenance  is  required,  it  should  be  performed  by  certified  trained 

persons  having  proper  equipment.  Fire  extinguishers  are  pressure  vessels  and  must  be  treated  with 

respect  and  handled  with  care.  They  are  mechanical  devices  and  require  periodic  maintenance  to  be 

sure  that  they  are  ready  to  operate  properly  and  safely.    Victory  strongly  recommends  that  the 

maintenance  of  portable  fire  extinguishers  be  done  by  a  trained  professional  –  your  local  authorized 

Victory Distributor.   

 

Victory  Corporation  makes  original  factory  parts  available  to  ensure  proper  maintenance  – 

USE  OF 

SUBSTITUTE PARTS RELEASES VICTORY OF ITS WARRANTY OBLIGATIONS.

    Victory 

parts  have  machined  surfaces  and  threads  that  are  manufactured  to  exacting  tolerances.    O-rings, 

hoses,  nozzles,  and  all  metal  parts  meet  precise  specifications  and  are  subjected  to  multiple  in-house 

inspections  and  tests  for  acceptability.    Only  spare  parts  listed  in  appendix  A  should  be  used. 

DO 

NOT SUBSTITUTE

.   

WARNING 

Do not use this extinguisher on class D fires or flammable materials that react with water.   

Protect extinguisher from freezing.   

Never include Calcium Chloride within water content

 

RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE 

Содержание WM2.5GAL

Страница 1: ...at they are ready to operate properly and safely Victory strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your local authorized Victory Distrib...

Страница 2: ...D FAILURE TO HEED THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY VICTORY ASSUMES NO LIABILITY FOR SERVICE MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS MANUAL REFERENCES IN THIS...

Страница 3: ...to 49 C please see the nameplate on your extinguisher The extinguisher should be adequately protected if temperatures outside of this range are anticipated Keep the extinguisher clean and free from d...

Страница 4: ...the extinguisher in a vertical position aim the nozzle at the base of the fire 5 Approach fire from upwind minimum of 10 feet of the front edge of the fire 6 Starting back from this distance squeeze t...

Страница 5: ...sher connected to a regulator of a high pressure source for an extended period A defective regulator could cause the cylinder to rupture due to excessive pressure CAUTION Discharge time and effective...

Страница 6: ...ondition to prevent its operation and any necessary repair or replacement It will normally reveal if hydrostatic testing or internal maintenance is required Maintenance servicing recharging shall be p...

Страница 7: ...te the class C capability Do not mix deionized water with non deionized in extinguisher content 6 Visually inspect the pressure gauge a If bent damaged or improper gauge depressurize and replace b If...

Страница 8: ...could seriously damage the plastic gauge face 3 Inspect the extinguisher for damaged missing or substitute parts NOTE Only factory replacement parts are approved for use on victory fire extinguishers...

Страница 9: ...disassembled valve with a soft bristle brush or soft cloth Blow the valve out with air or nitrogen Inspect the collar O ring valve stem spring and dip tube assembly and replace parts if worn or damage...

Страница 10: ...ing facing the front of the extinguisher gauge side 12 Install new tamper seal wrapping through loop and around levers to secure ring pin Do not over stress tamper seal 13 Weigh assembled extinguisher...

Страница 11: ...ent De pressurize and replace Install the correct Victory pressure gauge using Teflon tape on the gauge threads 9 Gauge does not indicate compatible with brass De pressurize and replace Install the co...

Страница 12: ...will not affect the remainder Victory is not responsible for the installation or the maintenance of the products Defective products for which a valid claim has been made shall be returned to Victory s...

Страница 13: ...sociation 2022 Edition 1 Batterymarch Pk P O Box 9101 Quincy MA 02169 7471 www nfpa org CGA C 1 Methods for Hydrostatic Compressed Gas Assoc Inc Testing of Compressed Gas 4221 Walney Road 5th floor Cy...

Страница 14: ...14 APPENDIX A...

Страница 15: ...ch Pressure Gauge to valve Recommended torque 5 12Nm 44 106 in lbs with sealant glue Scales Filling cylinders with deionized water Recommended accuracy 2 5 or better Pressurizing recharging adaptors S...