Appendix №2
INSTRUCTION
for installation and operation of wood-burning stoves and fireplaces
with integral boilers
Your appliance with an integral boiler is designed to work in a water heating system under the maximal operation pressure:
for “open” system under 1 bar;
for “close” system under 2 bar;
In the combustion chamber of the appliance, there is an integral boiler with heat output according to Appendix №1.
The maximum allowed temperature value of the water in the boiler should be 85°С.
When connecting the heating system the following rules and recommendations should be observed:
An appliance with an integral boiler should be assembled by authorized organization only!
Before connecting the installation, it is advisable to calculate the heat loss in the particular case.
In case of connecting loads
with greater heat output, than the declared one in the referent appendix, a cooling down of the heating surfaces of the
integral boiler occurs, which leads to condensation and pitching;
At “open” water heating system
the installation should be connected to the atmosphere with an opened expansion container,
mounted above the highest heating device. Between the appliance and the expansion container not any blocking components
should be connected.
At “closed” water heating system
safety components should be integrated into the installation, which does not allow
exceeding of the working pressure in the appliance over 2 bar.
Deaeration in each branch and component of the installation should be ensured, in each moment of its operation, and the
appliance as well;
In the installation, immediately near the integral boiler, in the lowest point, drains tap not less than ½” should be mounted;
All components of the installation should be ensured against freezing, especially if the expansion container or other parts of it
are situated in non-heated rooms;
At installations with forced circulation, the pump should be ensured with long-term power supply device –automatic mode
(UPS). We recommend the circulation pump to be switched on and switched off by means of thermostat, doubled with manual
electric switch;
When an old installation is used, then it should be repeatedly washed from the accumulated filths, which could be precipitated
on the walls of the integral boiler;
The circulation water should not be drowned off the installation during the non-heating season.
For appliances with an integral boiler, it is better to clean the surfaces of the boiler from soot and resinous matters at least once a
month.
By inserting appropriate isolation materials between the wall and the radiators, you will achieve radiation heating with approved
advantages.
This water heater provides another opportunity -installing a coil into the boiler, for warm sanitary water.
The manufacturer cannot guarantee the work of the heating installation, except for the appliance. In case of incorrect
connecting caused by increased pressure an inflation of the integral boiler and welding rupture occur. The manufacturer
does not take any responsibility for such defects.
INSTALLATION DIAGRAM
for connecting of wood-burning stoves and fireplaces with integral boilers type “B” (open heating system)
1. Blocking valve
9. Overflow drain
2. Deaerator
10. Manometer
3. Radiator
11. Hot water pipes
4. Appliance
12. Cold water pipes
5. Collector
13. Pump
6. Pump thermoregulator
14. Filter
7. Thermometer
15.Turn cock for filling and
8. Opened Expander tank
draining the system