background image

I-VICFLEX.AQD-M

INSTALLATION INSTRUCTIONS

Victaulic

®

 VicFlex

 Sprinkler Fittings for Metal Duct Applications 

Style AQD-M Bracket

I-VICFLEX.AQD-M_1

REV_B

 WARNING

•  Read and understand all instructions before attempting to install any Victaulic products.
•  Always verify that the piping system has been completely depressurized and drained immediately prior 

to installation, removal, adjustment, or maintenance of any Victaulic products.

•  Confirm that any equipment, branch lines, or sections of piping that may have been isolated for/

during testing or due to valve closures/positioning are identified, depressurized, and drained 
immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products.

•  Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious  personal injury and property damage.

     

•  This Victaulic

®

 VicFlex

 product shall be used only in fire protection systems that are designed and installed in accordance with current, 

applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with 
applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing 
temperatures, corrosion, mechanical damage, etc.

•  These installation instructions are intended for an experienced, trained installer. The installer shall understand the use of this product and 

why it was specified for the particular application.

•  The installer shall understand common industry safety standards and potential consequences of improper product installation.
•  It is the system designer’s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the 

piping system and external environment.

•  The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and 

flow rate on stainless steel components to confirm system life will be acceptable for the intended service.

Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system 
failure, resulting in death or serious personal injury and property damage.

Flexible Hose Listing and Approval Information

Flexible Hose

AH2-CC

With AQD-M

NOTE:

 Victaulic

®

 VicFlex

 flexible hoses are City of Los Angeles 

(RR5659) Approved, accepted for use by the City of New York 

Department of Buildings (MEA 60-05-E), and have the OSHPD Pre-
Approval (OPA-2255-07).

Maximum Working Pressure Rating of Flexible Hose:

    200 psi/14 Bar/1379 kPa (FM) 

 

Maximum Ambient Temperature Rating of Flexible Hose:

    225° F/107° C (FM)

Connection to Sprinkler Piping:

  1 inch/DN25 IGS (FM)

Minimum Bend Radius of Flexible Hose:

 

7 inch/178 mm (FM – Series AH2-CC)  

 

Maximum K-Factor of Sprinkler to be Connected to Sprinkler 

Reducing Nipple:

  Refer to footnotes in the “Friction Loss Data” section.

Maximum Number of 90° Bends Per Flexible Hose:

 

Refer to the “Friction Loss Data” section.

Flexible Hose Bend Characteristics:
 NOTE:

 Care shall be taken to avoid torquing the flexible hose.

90°

OR

OR

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

2X

Minimum 

Bend

Radius

2X

Minimum 

Bend

Radius

SCAN QR CODE FOR ACCESS TO THE FULL 

I-VICFLEX.BRG BEND RADIUS GUIDE INSTRUCTIONS 

ON VICTAULIC.COM

Содержание VicFlex I-VICFLEX.AQD-M

Страница 1: ...product installation It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the effect of chemical composition pH level operating temperature chloride level oxygen level and flow rate on stainless steel components to confirm system...

Страница 2: ...rinkler system piping to domestic hot water systems DO NOT allow electrical wiring or other cabling to be hung or wrapped around the sprinkler piping system DO NOT install sprinklers and sprinkler fittings where ambient conditions may fall below or exceed the maximum listed or approved temperature ratings The flexible hose shall not be bent or fluctuated up and down or side to side when pressurize...

Страница 3: ... 1 2 3 4 Item Series AH2 CC Description 1 Flexible Hose Assembly 2 Coupling Assembly 3 Identification Sleeve 4 No 140 Male NPT or BSPT Thread x Groove Adapter Nipple See Note Above BRACKET ASSEMBLY DRAWINGS Refer to pages 7 8 of this manual for bracket installation instructions Style AQD M Bracket 2 4 5 3 1 3 2 4 1 5 Item Style AQD M Description 1 Bracket 2 Sprinkler Reducer 3 Coupling Assembly 4 ...

Страница 4: ...E below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excessive lubricant on the gasket sealing lips Failure to use a compatible lubricant may cause gasket damage resulting in joint leakage and property damage 3a If any conditions listed in the NOTICE below are met apply a th...

Страница 5: ... Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the nut after metal to metal bolt pad contact is achieved If you suspect that any hardware has been over tightened as indicated by a bend in the bolt bulging of the nut at the bolt pad interface or damage ...

Страница 6: ... 5 Insert the inlet end of the Series AH2 CC Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gasket is seated fully in the gasket pocket of each housing and that the housings keys engage with the spacer on the inlet end of the Series AH2 CC Flexible Hose 5a Reinstall the two bolts and nuts that were removed in step 4 NOTE Verify that the oval neck of each bolt seats p...

Страница 7: ...n Connect the nut to the sprinkler reducer DO NOT use pipe joint compound or PTFE thread sealant tape on the fine threads The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approximately 1 2 to 3 4 of a turn past hand tight NOTE To prevent damage to the seal tighten the assembly by applying torque only to the con...

Страница 8: ...racket as a template drill a 3 16 hole at each location 4a Install a 3 16 stainless steel domed head sealing blind rivet recommended into each drilled hole NOTE Hardware is not included and shall be stainless steel or a material suitable for the application 4b Four stainless steel 10 Type AB self tapping metal screws can be used instead of rivets When using self tapping sheet metal screws holes do...

Страница 9: ...on of the I 109 installation instructions 5a For applications where a Style 005 FireLock Rigid Coupling with silicone gasket is required refer to the current version of the I 100 Field Installation Handbook for instructions For silicone gaskets use Victaulic Lubricant or a silicone compatible lubricant DO NOT use silicone lubricant on silicone gaskets 6 Apply the duct mastic sealant to cover over ...

Страница 10: ...The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publication 25 14 which can be downloaded at victaulic com Spacer Inspect Inlet End of Flexible Hose 5 Inspect the end of the Series AH2 CC Flexible Hose to verify that there is no damage dents crushed edges etc A new Vic...

Страница 11: ...mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH2 CC 48 48 1220 1 2 DN15 23 4 3 7 1 7 inch 178 mm minimum bend radius tested with standard 53 4 inch 146 mm length straight reducer A higher number of bends may be permitted provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends e g Two ...

Страница 12: ...M Bracket For complete contact information visit victaulic com I VICFLEX AQD M 14906 REV B UPDATED 07 2020 Z000AQDM00 VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND OR OTHER COUNTRIES 2020 VICTAULIC COMPANY ALL RIGHTS RESERVED ...

Отзывы: