I-VIC300MS
/ Vic-300
®
MasterSeal
™
Butterfly Valves
/ Installation and Maintenance Instructions
2 . Loosen the set screw on the side of the handle (Item 1), as shown
above .
2a . Remove the Lever Lock Handle assembly from the plate .
NOTICE
• The stem contains a key that is essential for re-installation of a
handle or a gear operator. Use care to prevent misplacement of
this key.
3 . Remove the hex nuts (Item 5) and lock washers (Item 4) from the
two hex-head screws (Item 3) . In addition, remove the hex nut
(Item 5) and lock washer (Item 4) from the hex-head screw (Item
6) to permit removal of the plate from the valve body mounting
flange .
4 . Remove the plate (Item 2) from the valve body mounting flange .
5 . The valve is now ready for conversion to a Tamper-Resistant
Handle or a Gear Operator . In addition, the “Stem Seal
Replacement” instructions can be performed, the thermal barrier
kit can be installed, or the insulation extension kit can be installed .
CAUTION
• DO NOT attempt to operate a Series 761 or 461 Butterfly Valve
without a handle or gear operator installed.
Failure to follow this instruction will cause improper valve operation
and damage to the stem.
I-VIC300MS_13
victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2014 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV_F