REMOVING THE SYSTEM FROM SERVICE

1. 

notify the authority having jurisdiction, remote station alarm 
 monitors, and those in the affected area that the system is being 
taken out of service.

2.  close the water supply main control valve to take the system out of 

service.

3.  open the system main drain valve, and allow the system to drain 

completely. 

NOTE:

 it may be necessary to open the remote system 

test valve (inspector’s test connection) and any auxiliary drains in 
order to drain the system completely.

INSTALLATION OF THE AUXILIARY WATER MOTOR ALARM 

TEST VALVE KIT

 WARNING

•  Make sure the valve is depressurized and 

drained before attempting to remove any 
trim from the valve.

Failure to follow this instruction could result 
in serious personal injury and/or property 
damage.

1. 

make sure the valve is completely depressurized and drained.

2.  remove the trim at the locations designated in the exploded view 

drawing on page 1.

3.  apply a small amount of pipe joint compound or teflon* tape to 

the external threads of all threaded pipe connections contained in 
the kit. do not get any tape, compound, or other foreign material 
into the pipe connections.

4.  install the kit components, as shown in the exploded view drawing 

on page 1.

5.  place the system back in service by following the “placing 

the system in service” section of the i-751.Vds installation, 
maintenance, and testing manual.

6.  check the connections for any leaks. if any leaks are present, 

depressurize and drain the system and repair any leaks.

* Teflon is a registered trademark of the DuPont Company

I-751.VDS/KIT_2

Series 751 FireLock European Alarm Check Valve Stations

AUXILIARY WATER MOTOR ALARM TEST VALVE KIT

I-751.VDS/KIT

KIT INSTALLATION INSTRUCTIONS

www.victaulic.com