PERFORMING THE WATER MOTOR ALARM TEST

1. 

notify the authority having jurisdiction, remote station alarm 
monitors, and anyone in the affected area that the water motor 
alarm test will be performed.

2.  Verify that the alarm line ball valve is open.
3.  open the auxiliary water motor alarm test ball valve.
3a.  confirm that mechanical and electrical alarms are activated and 

that remote monitoring stations, if provided, receive an alarm 
signal. 

NOTE:

 there may be a time delay if a series 752 retard 

chamber is installed.

4.  close the auxiliary water motor alarm test ball valve after proper 

operation of all alarms is verified.

5.  confirm that all valves are in their normal operating positions (refer 

to table below).

Valve

Normal Operating Position

System Test Valve

Closed

System Main Drain Valve

Closed

Water Supply Main Control Valve

Open

Alarm Line Ball Valve

Open (Lockable)

Auxiliary Water Motor Alarm Test Ball Valve

Closed (Lockable)

WAT ER  MOTOR

ALARM

S E R IE S 760

R

F M

APP ROV E D

VdS

To

System

Water

Supply

To

Drain

Alarm Line Ball

Valve (Normally

Open Lockable)

System Test Valve

(Normally Closed)

Water Supply Main

Control Valve

System Main Drain

Valve (Normally Closed)

Auxiliary Water Motor

Alarm Test Valve

(Normally Closed Lockable)

I-751.VDS/KIT_3

Series 751 FireLock European Alarm Check Valve Stations

AUXILIARY WATER MOTOR ALARM TEST VALVE KIT

I-751.VDS/KIT

KIT INSTALLATION INSTRUCTIONS