VD530 Series Inverter User Manual Function Parameter Table
- 67 -
F9-29
Power on Time
Upon the First
Time Fault
-
-
●
F9-30
Running Time
Upon the First
Time Fault
-
-
●
F9-33
Fault Automatic
Reset Times
0~20
0
○
F9-34
Fault Automatic
Reset Interval
Time
0.1s~100.0s
1.0s
○
F9-35
Fault DO Action
Selection During
the Fault
Automatic Reset
0: No action
1: Action
0
○
F9-36
Fault Protection
Action Selection
1
Unit’s digit: motor overload (11)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: input phase loss (13)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: output phase loss (14)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: external fault (17)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten thousand’s digit: communication
abnormal (18)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
0x00000
○
F9-37
Fault Protection
Action Selection
2
Unit’s digit: encoder / PG card abnormal
(31)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: parameter read-write
abnormal (21)
0: Coast to stop
1: Stop according to stop mode
0x00000
○